Programming i/o module operation p, Interfacing ts-lld to tank gauge p, Interfacing ts-lld to tank gauge – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Setup Programming Guide User Manual
Page 15

PREFACE
Page
P - vii
P
Standard and
Optional
Output Devices
NOTE
ProgrammingI/O Module Operation
The TS-CIM / TS-IEM channels * can function either as an input or an output module. The
mode menu option allows selection of the channel operation — this must correspond to the
type of module that is inserted into the channel. Input mode must be selected for input
modules, and output mode must be selected for output modules.
Reference the Chapter
about
IO MODULE
setup programming.
Aux. Inputs are always inputs and cannot be changed because the input circuitry
is hard-wired.
Reference the Chapter about
AUX INPUT
setup programming.
Interfacing TS-LLD to Tank Gauge
In order to interface the
INCON
TS-LLD line leak detector(s) to the TS-1001/504 / 2001/
508 / Tank Sentinel consoles —
Use the TS-LLD interface terminals within the console
(providing RS-485 bidirectional
communication). The first TS-LLD is wired to the tank gauge and the others are connected
to each other (1 to 2, 2 to 3... ).
LLD
is available with Tank Sentinel software version #
1.10 and higher ( check options –
L
must be in the part number ).
Standard Output Devices:
Modulated Annunciator
Solid Annunciator
Relay 1
Relay 2
Optional Output Devices:
TS-ROM Relay 1
TS-ROM Relay 2
TS-ROM Relay 3
TS-ROM Relay 4
TS-ROM Relay 5
TS-ROM Relay 6
TS-ROM Relay 7
TS-ROM Relay 8
Optional (TS-CIM / TS-IEM) Output Devices
:
I/O Module Output 1*
I/O Module Output 2*
I/O Module Output 3*
I/O Module Output 4*
I/O Module Output 5*
I/O Module Output 6*
I/O Module Output 7*
I/O Module Output 8*
I/O Module Output # 9* I/O Module Output # 10*
I/O Module Output # 11* I/O Module Output # 12*
I/O Module Output # 13* I/O Module Output # 14*
I/O Module Output # 15* I/O Module Output # 16*
I/O Module Output # 17* I/O Module Output # 18*
Note
: The TS-2001 will list the
TS-CIM Output Modules as I/0
Module - Outputs # 17 through
# 24 (if installed).
I/O Module Output # 19* I/O Module Output # 20*
I/O Module Output # 21* I/O Module Output # 22*
I/O Module Output # 23*
I/O Module Output # 24*