4.1.1

Local Automatic Operation

With the LOCAL-REMOTE-OFF (L-R-O) switch in the
LOCAL position check that the LED indicators on the
Operator Interface Panel (OIP) are as follows:

LED

Condition

Meaning

Start/Stop

Flashing Green

System is stopped.
No pumps running.

Pump 1 On/Off

Flashing Green

Pump1 is enabled
but not on.

Press the START/STOP key. The flashing green LED
will turn solid green. After a brief delay the Pump 1
LED will turn solid green indicating that it is running
variable speed. It will then try to maintain setpoint by
varying pump speed.

4.1.2

Remote Automatic Operation

With the LOCAL-REMOTE-OFF (L-R-O) switch in the
REMOTE position check that the LED indicators on
the Operator Interface Panel (OIP) are as follows:

LED

Condition

Meaning

Start/Stop

Flashing Green

System is stopped.
No pumps running.

Pump 1 On/Off

Flashing Green

Pump1 is enabled
but not on.

If a pump is not running this means the remote start
contact (from the energy management system or
other source) is not closed and the controller has not
been given a start signal.

Once operating in remote it is possible to stop opera-
tion (i.e., override the remote start command) by
either turning the L-R-O switch to off or by pressing
the START/STOP key on the OIP. It is recommended
to TURN THE L-R-O SWITCH TO OFF to stop the
system if it is running in remote.

4.2

A1 OPERATION

Confirm the setup of the following items:

Section

Item

Value

3.5.3

Total # of pumps

1

3.7.1

PV stage speed %

0

3.7.1

EOC pump max. flow

0

3.11.1

Number of pumps in bypass

1

4.2.1

Local Automatic Operation

With the LOCAL-REMOTE-OFF (L-R-O) switch in the
LOCAL position check that the LED indicators on the
Operator Interface Panel (OIP) are as follows:

LED

Condition

Meaning

Start/Stop

Flashing Green

System is stopped.
No pumps running.

Pump 1 On/Off

Flashing Green

Pump1 is enabled
but not on.

Press the START/STOP key. The flashing green LED
will turn solid green and the message STARTUP-
STANDBY
will be displayed. After a brief delay the

Pump 1 LED will turn solid green indicating that it is
running variable speed. It will then try to maintain set-
point by varying pump speed.

4.2.2

Remote Automatic Operation

With the LOCAL-REMOTE-OFF (L-R-O) switch in the
REMOTE position check that the LED indicators on
the Operator Interface Panel (OIP) are as follows:

LED

Condition

Meaning

Start/Stop

Flashing Green

System is stopped.
No pumps running.

Pump 1 On/Off

Flashing Green

Pump1 is enabled
but not on.

If a pump is not running this means the remote start
contact (from the energy management system or
other source) is not closed and the controller has not
been given a start signal.

Once operating in remote it is possible to stop opera-
tion (i.e., override the remote start command) by
either turning the L-R-O switch to off or by pressing
the START/STOP key on the OIP. It is recommended
to TURN THE L-R-O SWITCH TO OFF to stop the
system if it is running in remote.

4.4

B3 OPERATION

Confirm the setup of the following items:

Section

Item

Value

3.5.3

Total # of pumps

2

3.7.1

PV stage speed %

0

3.7.1

EOC pump max. flow

0

3.11.1

Number of pumps in bypass

1

4.4.1

Local Automatic Operation

With the LOCAL-REMOTE-OFF (L-R-O) switch in the
LOCAL position check that the LED indicators on the
Operator Interface Panel (OIP) are as follows:

LED

Condition

Meaning

Start/Stop

Flashing Green

System is stopped.
No pumps running.

Pump 1 On/Off

Flashing Green

Pump1 is enabled
but not on.

Pump 2 On/Off

Flashing Green

Pump2 is enabled
but not on.

Take note of the pump sequence. Only the first pump
in the sequence will run in normal operation. The sec-
ond pump is a standby and will run only if the duty
fails. To change which pump is the duty pump press
the ALTERNATION/4 key.

Press the START/STOP key. The flashing green LED
will turn solid green and the message STARTUP-
STANDBY
will be displayed. After a brief delay the
duty pump LED will turn solid green indicating that it
is running variable speed. It will then try to maintain
setpoint by varying pump speed.