Bell & Gossett S13641B Technologic 5500 Series Pump Controller User Manual
Page 12

12
3.5.2
The display will show:
# PUMPS = #
P1: *
P2: *
P3: *
P4: *
P5: *
P6: *
OK ? (Y/N)
* The pump status will be displayed for each defined
pump. The valid options are as follows:
N/A = pump not available as defined by setup
Rdy = pump available, not running
On = pump is running
Off = pump disabled, will not be allowed to start
Press the YES/7 and ENTER keys to accept pump
configuration and return to setup selection screen.
Press the NO/0 and ENTER key to set up any pumps.
3.5.3
The screen will now display:
TOTAL # PUMPS = #
Press the numeric key for the total number of pumps
(1 to 6 pumps). Press ENTER to continue.
3.5.4
The screen will now display:
EDIT PUMP ? (Y/N)
Press the YES/7 and ENTER keys if any of the pumps
must be set up.
Press the NO/0 and ENTER keys to return to the
pump status screen and return to section 3.5.2.
3.5.5
The display will show:
EDIT PUMP # #
Press the numeric key(s) for the pump you wish to set
up. The pump number is limited to the maximum
number of pumps. Press the ENTER key to proceed
with the set up.
3.5.6
The screen will now display:
PUMP # #
ENABLE/DISABLE: #
1=ENABLE 0=DISABLE
Press the PROCESS VARIABLE/1 and ENTER keys if
the pump will be enabled.
Press the NO/0 and ENTER keys if the pump will be
disabled.
3.5.7
The screen will now display:
DO ANOTHER ? (Y/N)
Press the YES/7 and ENTER keys to set up another
pump. Return to section 3.5.5 and repeat for all
remaining pumps.
Press the NO/0 and ENTER keys to return to the
pump status screen and return to section 3.5.2.
3.6
SYSTEM SETUP
3.6.1
Press the SETUP/3 key at the setup selection menu.
Press the ENTER key.
3.6.2
The display will now show:
SELECTION: #
0 = EXIT
1 = STAGE/DESTAGE
2 = PID
3 - ALARMS
Press the NEXT SCREEN key.
The display now shows:
SELECTION: #
0 = EXIT
4 = ALTERNATION
5 = BYPASS
6 = AFD
Press the NEXT SCREEN key.
The display now shows:
SELECTION: #
0 = EXIT
7 = DATE/TIME
8 = PASSWORD
9 = I/O SETUP
Press the NEXT SCREEN key. The display now
shows:
SELECTION: #
0 = EXIT
10 = COMMUNICATION
11 = SPECIAL FUNCTIONS
12 = CHANGE LANGUAGE
Press the NEXT SCREEN key. The display now
shows:
SELECTION: #
0 = EXIT
13 = SAVE TO FLASH
14 = LOAD FROM FLASH
15 = SET BRITE/CNTRST
Use the appropriate numeric key to select the setup
menu desired, press the ENTER key. A detailed
description of each menu follows.
DANGER: High voltage 3 phase power can kill.
Pumps can start automatically. Disconnect and lock-
out power prior to servicing pumps. FAILURE TO FOLLOW
THESE INSTRUCTIONS COULD RESULT IN SERIOUS
PERSONAL INJURY, DEATH, AND/OR PROPERTY
DAMAGE.