beautypg.com

Bell & Gossett S13641B Technologic 5500 Series Pump Controller User Manual

Page 24

background image

24

3.23.2

Press the F1/5 key at the Setup Selection menu.
Then press the ENTER key.

3.23.3

The display will show:

*WARNING*
ALL SETUP DATA WILL BE OVER WRITTEN.
PROCEED: ? (Y/N)

Press the NO/0 key to exit the default setup menu
and save all current factory/field variables. Press the
YES/7 key to load all of the pre-defined default vari-
ables. Once the variables are loaded the controller
will return to the display screen that was present prior
to entering the setup menu.

3.23.4

After setting the default values proceed with complet-
ing the system setup per Sections 3.4 to 3.18.

Section 4 - Operation

4.0

TYPE OF PROGRAM

There are nine operational programs with the
Technologic 5500 family of controls. Refer to the
nameplate on the front of the controller to determine
which program has been furnished.

B&G

No. of

Bypass

Program

Pumps Provided

Description

A0

1

No

One Pump/One AFD

A1

1

Yes

One Pump/One AFD

Constant speed or variable
speed operation

B3

2

Yes

Two Pumps/One AFD

Either pump operating
constant speed or variable
speed.

C0

2

No

Two Pumps/Two AFDs

Two 100% duty pumps and
AFDs without staging.

D0

2

No

Two Pumps and AFDs

Both pumps may stage and
run variable speed.

D4

2

Yes

Two Pumps and AFDs

Both pumps may stage
and run variable speed
or constant speed.

NOTE: Constant Speed refers to across-the-line operation.

4.0.1

Normal Scrolling Operation

Other screens may be viewed by scrolling from the
Technologic Pump Controller screen shown below:

TECHNOLOGIC

PUMP CONTROLLER
MM/DD/YY HH:MM:SS
STATUS MODE

The status portion of the display indicates the current
alarm status. If NORMAL is displayed there are no
alarms. If *ALARM* is displayed there are alarms that
may prevent normal operation, refer to Section 4.15
for additional information.

The mode portion of the display indicates the current
auto/manual mode of operation. The following table
indicates all possible options:

Sections for

Additional

Mode

Description

Infomation

AUTO

Pump Controlled by

4.1 - 4.7

Controller

MANUAL

Variable Speed Pumps

4.11

Controlled by User

MAN. BPS

Constant Speed Pumps

4.10

Controlled by User

4.0.2

Press the NEXT SCREEN key.

The display now shows:

PUMP STATUS

P1:(RDY or N/A)P2: (RDY or N/A) P3:(RDY or N/A)
P4:(RDY or N/A)P5: (RDY or N/A) P6:(RDY or N/A)
STATUS

MODE

Press the NEXT SCREEN key.

The display now shows:

ACTIVE VALUES

Zone: ##

Speed: ###%

Seq: #
STATUS

MODE

Press the NEXT SCREEN key.

The display now shows the following if any of the
transmitters are set up:

FLOW RATE: #### GPM
TOTAL KW: ###
SYS DP: ##

EFF: ## %

STATUS

MODE

Press the NEXT SCREEN key.

The display now returns to the Technologic Pump
Controller screen.

4.1

A0 OPERATION

Confirm the setup of the following items:

Section

Item

Value

3.5.3

Total # of pumps

1

3.7.1

PV stage speed %

0

3.7.1

EOC pump max. flow

0

3.11.1

Number of pumps in bypass

0