Bell & Gossett S13641B Technologic 5500 Series Pump Controller User Manual
Page 23

23
3.22
TESTING INPUTS AND OUTPUTS
3.22.1
At the Setup Selection menu, press the ALTER-
NATION/4 and ENTER keys.
3.22.2
The display will show:
TEST SELECTION: #
1=DI
4=AO
7=DISP
2=DO
5=LED
8=COMM
3=AI
6=KEY
0=EXIT
3.22.3
Press the PROCESS VARIABLE/1 and ENTER keys
to test digital inputs.
The display will now show:
DIGITAL INPUTS
SLOT 0 1
SLOT 1-4 1
1234567890
1234567890
0000000000
0000000000
The zero below each corresponding input will change
to a one upon receiving a digital input.
“A” signifies the inputs at the first digital input module
and “B” signifies the inputs at the second digital input
module.
Press clear to exit the test.
3.22.4
At the Test Selection screen, press the SET POINT/2
and ENTER keys to test digital outputs.
The display will now show:
DO SLOT 2-x
1 2 3 4 5 6 7 8
x x x x x x x x
Enter DO# 0
(0 = EXIT)
The “x” will be replaced by the current state of the
specific digital output channel. An “0” indicates that
the relay is de-energized and a “1” indicates that the
relay is energized which will change the state of the
contacts.
Press any numeric key numbered 1-8. To change the
state of the digital output press the ENTER key. To
exit press “0” followed by the ENTER key.
3.22.5
At the Test Selection screen, press the SETUP/3 and
ENTER keys to test analog inputs.
The display will now show:
Analog Inputs:
1: ###% 4: ###% 7: ###%
2: ###% 5: ###% 8: ###%
3: ###% 6: ###% 9: ###%
The current % of span signal will be indicated next to
each input 0% = 4mA and 100% = 20mA.
Press clear to exit the test.
3.22.6
At the Test Selection screen, press the ALTER-
NATION/4 and ENTER keys to test analog outputs.
The display will now show:
A01 ###%
A04 ###%
A02 ###%
A05 ###%
A03 ###%
A06 ###%
EXIT ? (Y/N)
The ### will be replaced by the actual digital output
signal in %. The cursor will be flashing at the A01
value. Enter an alternate value by using the numeric
keys and press ENTER to output the new value or
press ENTER to move to the next channel.
This menu will only allow you to modify the output
signals that are connected to the system, therfore
A03 - A06 may not be modified unless the cor-
responding output cards are attached to the system.
3.22.7
At the Test Selection screen, press the F1/5 key to
test the LED’s. All of the LED’s on the left key set turn
on, then turn off, then flash. The entire test takes 15
seconds to complete prior to returning to the Test
Selection menu. Press the CLEAR key at any time to
terminate the test and return to the Test Selection
menu.
3.22.8
At the Test Selection screen, press the F2/6 key to
test the keypad. The display will show:
KEY TEST
PRESS A KEY FOR TESTING
Press any key except for the CLEAR key and the dis-
play will confirm that the key is working by displaying
the key name. After all of the keys have been tested
press the CLEAR key to return to the Test Selection
menu.
3.22.9
At the Test Selection screen, press the YES/7 key to
test the display. The display will scroll ASCII charac-
ters from right to left. All four lines will be tested at
the same time. To exit the test press the CLEAR key
and return to the Test Selection menu.
3.22.10 When the controller is setup to communicate with the
building automation, press the INFO/8 key while at
the test selection screen, to test the RS communica-
tion. The display will show:
Test Communication
B&G Read #
B&G Write #
If the controller is communicating properly, the num-
bers will continue increasing in value. For Modbus
protocol the read and write numbers will be equal,
BACnet and Johnson N2 protocol the numbers will
not be equal. If the numbers are not increasing in
value then the controller is not communicating prop-
erly. If it is not communicating, check the wiring at
the terminal blocks and the RS communication card
mounted on the controller.
3.23
DEFAULT SETUP
3.23.1
In the event the user would like to change all of the
setup variables back to the default values the default
setup menu will complete the task. The default values
are defined in the tables included in Sections 3.7 to
3.18. In addition all sensor and pump setup informa-
tion will be erased.
Prior to completing the default setup it is strongly
recommended that all factory/field variables be
recorded for future reference. Use the “Field Value”
location in the tables shown in Sections 3.7 - 3.18 to
record your current data. Also record your sensor
and pump setup information on the wiring diagram
that was included with the unit.