STAGE/DESTAGE SETUP MENU ITEMS

Field

Menu Item

Variable

Default

Range

Value

Pv Stg

Stg Spd: ##%

95

0-100

The maximum speed at which the lead pump will operate
prior to starting a lag pump, %.

Pv Stg

Stg Proof Timer: ### s

30

0-999

Proof timer prior to starting lag pump, seconds.

Pv Stg

Stab Timer: ###s

60

0-999

Staging stabilization time, delay prior to calculating
destage value, seconds.

13

PV Destg

Destage: ###%

85

0-100

Enter the percentage of the stabilized speed at which
the lag pump will stop, %.

PV Destg

Destg Pr Timer: ### s

30

0-999

Proof timer prior to stopping lag pump, seconds.

PV Destg

HD Spd: ### %

50

0-100

The lowest speed at which parallel pumps will operate
prior to destaging the lag pump, %.

PV Destg

HD Pr Tm: ### s

30

0-999

The proof timer prior to destaging the lag pump when operating
below the HD speed, seconds.

EOC Stg

Pump Max Flow: #####

0

0-65,535

The maximum flow allowable prior to starting a lag pump, GPM.

EOC Stg

Stg Proof Tm: ###s

30

0-999

Proof timer prior to end of curve staging, seconds.

EOC Stg

Flow offset: ### gpm

0

0-999

Flow rate of constant speed pump supplying variable speed
pump, input only required on series pumping applications.
The flow rate of the constant speed pump is deducted from
the total system flow rate in order to provide end of curve
protection for the variable speed pump.

EOC Dest

Destage Flow: ### %

45

0-100

Enter the percent of stabilized flow at which the
lag pump is destaged, %.

EOC Dest

Destage Pr TM: ###s

30

0-999

Proof timer prior to destaging lag pump, seconds.

3.7

STAGE/DESTAGE SETUP

3.7.1

The first screen is displayed below:

SELECTION: #
1 = PV STG

2 = PV DESTG

3 = EOC STG

4 = EOC DEST

0 = EXIT

By pressing the appropriate numeric key and ENTER,
the setup can be completed. See the following table
for all Stage/Destage menu items.

When setting up the system, recording configuration
values in the ‘Field Value’ column allows this manual
to serve as a future reference.