3.8

PID SETUP

3.8.1

See the following table for all PID menu items.

3.9

ALARM SETUP

3.9.1

See the following table for all alarm menu items.

PID MENU ITEMS

Field

Menu Item

Variable

Default

Range

Value

PID

PID-P ###

200

0-999

Enter the desired proportional value.

PID

PID-I ###

5

0-999

Enter the desired integral value.

PID

PID-D ###

1

0-999

Enter the desired derivative value.

PID

Reversed ?

N

Y or N

Enter NO for direct acting control which increases output as process
variable falls below setpoint. Enter YES for reverse acting control
which increases output as process variable rises above setpoint.

PID

SP Deviation ###

0

0-999

Enter the value for the number of PV units at which a dead band
will be created around the setpoint. The PID will be modified within
the dead band per the index setting below.

PID

Index ###

0

0-999

Enter a value to buffer the response of the PID while operating
in the dead band defined above.
Index = 1 no impact
Index = 999 maximum buffer.

ALARM MENU ITEMS

Field

Menu Item

Variable

Default

Range

Value

Alarms

AFD Fail Pr Tm: ###s

20

0-999

The proof timer prior to setting the AFD fail alarm, seconds.

Alarms

Pump Fail Pr Tm: ###s

30

0-999

The proof timer prior to setting the pump fail alarm, seconds.

Alarms

O.L. Fail Pr Tm: ###s

10

0-999

The proof timer prior to setting the O.L. fail alarm, seconds.

Alarms

Reset Tm: ###s

10

0-999

The time delay between pressing the RESET key and
restarting the pumps in variable speed mode.
Allows for pump deceleration, seconds.