Bell & Gossett S13641B Technologic 5500 Series Pump Controller User Manual
Page 14

14
3.8
PID SETUP
3.8.1
See the following table for all PID menu items.
3.9
ALARM SETUP
3.9.1
See the following table for all alarm menu items.
PID MENU ITEMS
Field
Menu Item
Variable
Default
Range
Value
PID
PID-P ###
200
0-999
Enter the desired proportional value.
PID
PID-I ###
5
0-999
Enter the desired integral value.
PID
PID-D ###
1
0-999
Enter the desired derivative value.
PID
Reversed ?
N
Y or N
Enter NO for direct acting control which increases output as process
variable falls below setpoint. Enter YES for reverse acting control
which increases output as process variable rises above setpoint.
PID
SP Deviation ###
0
0-999
Enter the value for the number of PV units at which a dead band
will be created around the setpoint. The PID will be modified within
the dead band per the index setting below.
PID
Index ###
0
0-999
Enter a value to buffer the response of the PID while operating
in the dead band defined above.
Index = 1 no impact
Index = 999 maximum buffer.
ALARM MENU ITEMS
Field
Menu Item
Variable
Default
Range
Value
Alarms
AFD Fail Pr Tm: ###s
20
0-999
The proof timer prior to setting the AFD fail alarm, seconds.
Alarms
Pump Fail Pr Tm: ###s
30
0-999
The proof timer prior to setting the pump fail alarm, seconds.
Alarms
O.L. Fail Pr Tm: ###s
10
0-999
The proof timer prior to setting the O.L. fail alarm, seconds.
Alarms
Reset Tm: ###s
10
0-999
The time delay between pressing the RESET key and
restarting the pumps in variable speed mode.
Allows for pump deceleration, seconds.