1 safety distances – GE Industrial Solutions GERAPID 2607, 4207, 6007, 8007 with arc chutes 1X2, 1X4, 2X2, 2X3, 2X4 User Manual
Page 29

2010-06-07 S47183e rev.03
Design and specifications are subject to change without notice
29
5.1 Safety distances.
Units call in mm (inches)
Legend for dimensional drawings
K
Heat sink (for Gerapid 6007)
L
All openings respectively free areas on the top of the cubical shall be not less than 50%
M
Solenoid drive
P
Diameter 9 mm [0,35 in], Countersunk screw M8
S
Control box
Z
Connector
Type
Arc chute
Main-
Additional Deflector Safety distances / Insulated plates
Safety distances / Earthed plates
Gerapid
Connection
isolation
E
A
B
C
D
A
B
C
D
2607 / 4207
1x2
all
10 (0,4)
700 (27,6)
150 (5,9)
150 (5,9)
120 (4,7) 1000 (39,4) 300 (11,8) 300 (11,8) 300 (11,8)
1x3
all
1)
1)
1)
1)
1)
-
-
-
-
1x4
all
150 (5,9)
700 (27,6)
150 (5,9)
150 (5,9)
120 (4,7) 1350 (53,2) 450 (17,7) 450 (17,7)
200 (7,9)
2x2
all
80 (3,15) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1) 1350 (53,2) 450 (17,7) 450 (17,7) 300 (11,8)
2x3
all
80 (3,15) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1)
-
-
-
-
2x4
H / H
Plate
150 (5,9) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1)
-
-
-
-
2x4
H / H
Sidewalls
150 (5,9) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1)
-
-
-
-
2x4
SEL / H
Pan
150 (5,9) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1)
-
-
-
-
6007
1x2
V / V Heat sink
10 (0,4)
1000 (39,4) 300 (11,8) 300 (11,8)
180 (7,1)
-
-
-
-
1x3
1)
1)
1)
1)
1)
1)
1)
-
-
-
-
1x4
V / V Heat sink
150 (5,9) 1000 (39,4) 300 (11,8) 300 (11,8)
180 (7,1)
-
-
-
-
2x2
V / V Heat sink
80 (3,15) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1)
-
-
-
-
2x3
V / V Heat sink
80 (3,15) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1)
-
-
-
-
2x4
1)
1)
1)
1)
1)
1)
1)
-
-
-
-
8007
1x2
V / V Heat sink
10 (0,4)
1000 (39,4) 300 (11,8) 300 (11,8)
180 (7,1)
-
-
-
-
1x3
1)
1)
1)
1)
1)
1)
1)
-
-
-
-
1x4
1)
1)
1)
1)
1)
1)
1)
-
-
-
-
2)
2x2
V / V Heat sink
80 (3,15) 1000 (39,4) 180 (7,1)
180 (7,1)
180 (7,1)
-
-
-
-
2)
2x3
V / V Heat sink
80 (3,15) 1000 (39,4) 180 (7,1)
180 (7,1)
300 (11,8)
-
-
-
-
2x4
1)
1)
1)
1)
1)
1)
1)
-
-
-
-
1)
will be checked by customers order
2)
acc. IEC 947-2 / ks-setting <12 kA H…Horizontal terminal V...Vertical terminal SEL...Current measurement system type SEL