GE Industrial Solutions AF-300 P11 User Manual
Page 51
![background image](/manuals/295766/51/background.png)
4-14
Data subject to change without notice 7/07. © 2007 GE Drives
Data check (verify)
60.00
60.00
1.DATA SETTING
2.DATA CHECK
3. OPR MNTR
4. I/O CHECK
5. MAINTENANCE
6. LOAD FCTR
7. ALM INF
8. ALM CAUSE
> 9. DATA COPY
READ
30HP-2
WRITE
30 HP-2
VERIFY
COMPLETE
30 HP-2
VERIFY
30 HP-2
VERIFY
30HP-2
Drive type of data stored in
the keypad panel
Mode (data check)
Data check in
progress
Data check complete
Error processing
30HP-2
WRITE
INV RUNNING
WRITE
MEMORY ERROR
50HP-2
WRITE
ERR-F25
1. Change disabled during operation
If a write operation is attempted during a drive
operation, or vice versa, the error message below
will appear. After stopping the drive and pressing
RESET
retry the write operation.
2. Memory error
If a write operation is attempted while data has not been
saved (i.e. no data) in the keypad panel data memory
during the read mode or when the drive type of data
read by keypad panel is different from the drive type to
which data is to be written, the following error message
will appear.
3. Verify error
During a data check (verify) operation, if data stored
in the keypad panel differs from data stored in the
drive, the following error message is displayed to
indicate the function number. The data is sus-
pended. To continue the data check and check for
other mismatching data, press
FUNC
DATA
. To stop the
data check and switch to another operation, press
RESET
.
RUN
PRG > PRG MENU
F/D > LED SHIFT
FWD
PRG
FUNC
DATA
FUNC
DATA