GE Industrial Solutions OKCV3000CN DeviceNet User Manual
Page 48

GEl-100343
DnetStAuxCode
Meaning
0
No additional information
1
All available group 2 message identifiers have been allocated
2
Invalid initial comm characteristic attribute
3
All available group 1 message identifiers have been allocated
4
All available group 3 message identifiers have been allocated
5
Invalid value within the transportClass trigger attribute
6
An Apply request is sent to a Connection instance when it is in the Established or
Timed-out state
7
Illegal to send fragmented explicit Connection message
8
Connection object must be in Established state and must be Messaging type of
Connection_in_order to_send_a_cnxn-based_request
Cannot send cnxn-based request since a request is outstanding
9
10
Invalid instance identifier specified in received explicit message request
11
Explicit message request is directed at non-existent cnxn instance
12
A Create request can only be sent to the class, not a particular instance
13
ConfigCnxnndex already set
14
Unable to create cnxn class
15
Apply attribute cannot be sent to the cnxn class, only a specific instance
16
Invalid service code received in explicit message request
17
Class specified in received Cnxn Based Explicit request message does not exist
18
More than.2 group 2 object have been created
19
Maximum number of allocatable group 3 identifiers already allocated
20
Group specified in open messaging connection is invalid
21
Invalid service code received in received ucmm request message
22
Duplicate MacId check response has been received
23
Duplicate MacId check request has been received
24
Cannot send open cnxn-based request since a request is outstanding
25
A connection within the client is not available
26
Timerld not correct
27
expected packet rate not supported (is greater than maximum allowed)
28
No more Timer available
29
watchdog timeout action not correct
30
Watchdog time-out occured
31
UCMM time-out occured
32
Explicit time-out occured
33
Attempt to deallocate a CAN channel not allocated
34
No more CAN channel available
35
No more CAN channel available for transmission
36
CAN Interrupt register error
37
CAN is still in hardware reset
38
CAN status register error
39
Error on allocation
40
BusOff detected
41
Error on de-allocation
42
Too much data
43
Parameter object data type not correct
44
Connection path not correct
45
I/O length not correct
50
1st step of drive reset failed
51
2nd step of drive reset failed
52
3rd step of drive reset failed
400..499
This is the parameter IPA that caused the error
TNetl2O
APPENDIX B
S