Lyib, Rflx: read fixed word, Rfix – GE Industrial Solutions OKCV3000CN DeviceNet User Manual
Page 35

L)evlceiNet
5.7. RFlX: READ FIXED WORD
SYMBOL:
0
2
3
RFIX
FUNCTION:
This block is used on
the server device to read one (or two) words of FWA and to write the value in a defined
xVAR. Note that the client is able to write only
in the FWA of the server. The type of var where the value is to be
copied is an input. It is possible to select integer type for IVAR or float type for VAR (in this case 2 words will
be read) .Note that this Brick acts internally to the slave DGFC, and no DeviceNet communication is involved.
md
name
type
description
D
Ind_fix
mt
0 ... 47; index of FWA, it is the Fixed Word (s) to
be read
1
Ind_var
mt
0... 199; Index of the xVAR wherethe value read
in FWA is written.
2
Type var
mt
Type of the xVAR read. The used values are:
3 = integer (IVAR)
7
float (VAR)
3
Tmo
mt
time-out [number
of execution Bricksj
TNet6O
BLOCK OUTPUT
md
name
type
description
mt
fresult: 0
new fixed value available
1= already read value on fixed area
2= time-out elapsed
Q
MAXIMUM NUMBER OF BLOCKS: 32
NOTE:
if you use WIIN+DRIYE, the
RFIX
functions are the same but change inputs
and output (see
the
DGFC
manual)
LYIB
HOW TO EXCHANGE 110 DATA
TNeI7O
md_fix
Indvar
Q
Type var
Tmo
BLOCK INPUT