GE Industrial Solutions LP33 Series 80 & 100 Installation Guide User Manual
Page 32
Modifications reserved
Page 32/47
OPM_LPS_3UI_80K_M10_1US_V010.doc
Installation Guide LP33 Series 80 & 100 UL S1
Mechanical assembly of the UPS and the battery cabinet 26” / 650mm
NOTE !
Mechanical assembly of the UPS and the battery cabinet must be performed by
QUALIFIED SERVICE PERSONNEL only.
The UPS cabinet and the battery cabinet must be installed on leveled floor.
UPS with battery cabinet 26” / 650mm
Bolt M8x25
tensilock
Detail showing the
mechanical assembly
of the UPS and battery cabinets 26"/650mm.
To bolt only on the front side.
Battery cabinet frame 26"/650mm
Nut M8 tensilock
UPS cabinet frame
Q2
I ON
0 O
FF
F11-12-13
FTM3
Q1
I ON
0 O
FF
UPS cabinet
Battery cabinet
26"/650mm
6.5"
165mm
37
.4
"
950mm
68.3
"
173
5m
m
A
A
A
LPS33U_080-100_UPS+Battery cabinet 0660_01
A
Fig. 3.9.3-1 Mechanical assembly of the UPS and the battery cabinet 26” / 650mm
Align the cabinets together, with the Battery cabinet on the left side. In case of multiple battery cabinets,
align first beside of the UPS the battery cabinets 26” and then left the wider battery cabinets 48”.
Pay attention, that no loose cables are trapped when pushing the cabinets together.
Join the cabinets with bolts trough the fixing holes as illustrated in drawing Fig. 3.9.3-1 and 3.9.3-2 /
detail A & B.
Once finally positioned, the two cabinets have to be connected together with the connection cables,
see Fig 3.9.3-3 (Battery cabinet 26”/650mm), Fig 3.9.3-4 (Battery cabinet 48”/1215mm) and Fig 3.9.3-
5 (Battery cabinet 26”/650mm and 48”/1215mm).
UPS with battery cabinet 26” / 650mm and 48” / 1215mm
LPS33U_080-100_UPS+Battery cabinet 1215_01
Detail showing the mechanical assembly
of the UPS and battery cabinets 26"/650mm or/and 48"/1215mm.
To bolt only on the front side.
Q2
I ON
0 O
FF
F11-12-13
Q1
I ON
0 O
FF
A
Battery cabinet
48"/1215mm
UPS cabinet
Battery cabinet
26"/650mm
Battery cabinet frame
Nut M8 tensilock
UPS cabinet frame or
battery cabinet frame
A
FTM3
6.
5"
165m
m
37
.4
"
950m
m
68.
3"
17
35m
m
A
A
A
Bolt M8x25
tensilock
A
FTM3
A
Fig. 3.9.3-2 Mechanical assembly of the UPS and the battery cabinet 26” / 650mm and 48” / 1215mm