GE Industrial Solutions LP33 Series 80 & 100 Installation Guide User Manual
Page 25
![background image](/manuals/295662/25/background.png)
Modifications reserved
Page 25/47
OPM_LPS_3UI_80K_M10_1US_V010.doc
Installation Guide LP33 Series 80 & 100 UL S1
Size of Branch Circuit Over current Protection - All Models:
"CAUTION - To reduce the risk of fire, only connect UPS to a circuit provided with (see below)
maximum amperes branch circuit over current protection in accordance
with the NEC (National Electric Code), NSI / NFPA 70
AC Input
AC Input Rectifier
AC Input Bypass
DC Input (*)
UPS Model
F1 F2 F3
FTM3
LP33 Series 80
350 A
350 A
350 A
400 A
LP33 Series 100
400 A
400 A
400 A
400 A
(*) Nominal voltage rating: 2 x 144Vdc
Wire sizing according to NEC Section 210-20 (a) Table 310-16
Use 167°F (75°C) copper wire
Wiring requirements:
AC INPUT:
3-Phase, 4 wire plus Ground
AC OUTPUT:
3-Phase, 4 wire plus Ground
DC INPUT:
3 wire (positive, negative and neutral) plus Ground
Maximum cable diameter that terminals can accept.
Refer to torque specifications table for torque requirements.
UPS Model
Rectifier Input
Bypass Input
DC Input
AC Output
GND
LP33 Series 80
4x(2xAWG 3/0)
4x(2xAWG 3/0)
3x(2xAWG 4/0)
4x(2xAWG 3/0)
AWG 2/0
LP33 Series 100 4x(2xAWG 4/0)
4x(2xAWG 4/0)
3x(2xAWG 4/0)
4x(2xAWG 4/0)
AWG 2/0