Installation Guide LP33 Series 80 & 100 UL S1
3.9.3 Battery connection
Before proceeding to a battery connection, follow the Safety Rules concerning the battery.
Make sure that the UPS is not powered and remove the external battery protections.
NOTE IN CASE OF EXTERNAL BATTERY !
To meet standards concerning electromagnetic compliance, the connection
between the UPS and external Battery must be done by using a shielded cable or
suitable shielded (metal) conduit!
Standard battery type for LP33 Series 80 & 100
Battery type
Technical Data
Manufacturer
UPS12-540MR HIGH RATE MAX
12Vdc 147Ah 100lbs/45kg
C & D Technologies, Inc.
List of possible battery configurations on LP33 Series 80 & 100
Autonomy (min.)
Battery cabinet / Width
Battery
type
Block
number 80kVA 100kVA
Note
One battery cabinet 26” / 650mm
147Ah
24
15
9
See Fig.
3.9.3-1 & 3
One battery cabinet 48” / 1215mm
294Ah
(2 x 147Ah)
48 41 30
See Fig.
3.9.3-2 & 4
One battery cabinet 26” / 650mm
One battery cabinet 48” / 1215mm
441Ah
(3 x 147Ah)
72 65 52
See Fig.
3.9.3-1 & 2 & 5
Two battery cabinet 48” / 1215mm
588Ah
(4 x 147Ah)
96 92 70
See Fig.
3.9.3-2 & 4 & 5
One battery cabinet 26” / 650mm
Two battery cabinet 48” / 1215mm
735Ah
(5 x 147Ah)
120 113 92
See Fig.
3.9.3-1 & 2 & 5
Three battery cabinet 48” / 1215mm
882Ah
(6 x 147Ah)
144 132 108
See Fig.
3.9.3-2 & 4 & 5