Rectifier – GE Industrial Solutions GPS4827 User Manual
Page 89
Galaxy Power System GPS4827
87
Rectifier
Rectifier Specifications
Electrical
Input
Voltage Range
95-275Vac, 2-wire, single phase
Frequency Range
45 - 66 Hz
Power Factor
> 0.98 at > 50% rated output
AC Surge Protection: It is important that ac surges reaching rectifiers do not exceed the capacity of the
rectifier internal surge protection. Protection must be provided external to the GPS system, if necessary,
to limit surge energy reaching the rectifiers. Site surge protection must be coordinated with rectifier
internal surge protection and must clamp at a lower voltage than the rectifier internal protection. The
internal protection voltage and current characteristics of the rectifiers are as follows:
Phase to Phase Voltage
MOV Conduction Current
320Vac (RMS)
0A
620V maximum clamping
1mA (DC test current)
810Vpeak
100A peak
Output
Internal Selective High Voltage Shutdown (ISHVSD)
High Voltage Shutdown (HVSD)
Float: 56.0Vdc Nom.
1,
2
Boost: 58.5Vdc Nom.
1,
2
Float: 57.00Vdc
Output
Output Power
2726W maximum
Output Current
1
50Adc maximum from -40°C to +55°C
30Adc at +75°C
Rectifier derates at approximately
1 ampere per degree C (+55°C to +75°C)
Float/Boost Voltage
44-58Vdc
Total Harmonic Distortion
<5% at full load
Regulation
±0.5%
Ripple
100 mVrms
Current Limit Set Point
15A-55A
1.
With Galaxy Millennium Controller
2.
Factory default settings – actual range is 44 - 58Vdc