GE Industrial Solutions GPS4827 User Manual
Page 73
Galaxy Power System GPS4827
71
cell battery voltage as a function of
temperature.
Enabled
Enables
or
Disables
the
Thermal
Compensation Feature. Move the cursor to
the field and use the <+> or <-> key to Enable
or Disable. Press
change.
High Temp
Comp
This
feature
allows
the
system
to
compensate for high temperatures.
Volt
Step
Down
Battery step temperature can be set from
113-185F. At this temperature, the system
voltage is reduced by 0.17 X # of cells/string.
High Comp
Limit
This sets the maximum temperature for
which thermal compensation is active.
Decrease
This sets the slope (mV/degC) for high
temperature compensation.
Nominal
Temp
This field set the temperature at which no
compensation is required. The system
voltage is at the setpoint float mode.
Low Temp Comp
This
feature
allows
the
system
to
compensate for low temperatures.
Low T Comp This enables or disables the low temperature
compensation feature.
Low Comp
Limit
This sets the minimum temperature for
which thermal compensation is active.
Increase
This sets the slope (mV/degC) for low
temperature compensation.
8.
Recharge Current
Limit
This feature sets the total amount of current
that will be allowed to recharge the batteries.
Limit
The configuration of this field enables or
disables the feature.
Limit to
This programmable value sets the maximum
amount of recharge current (in Amps) that
will be allowed for recharging the batteries.
The range is from 10 – 1000A.