57
Symbol
Default Designation
Default
Severity
Default LED Default Relay
ATF
Alarm Test Failed
Warning
None
None
BBL
Memory Backup Battery Low
Warning
None
None
BCA
Battery Type Conflict
Warning
None
None
BDA
Battery on Discharge
Major
BD
BD
BFA
Battery Test Failed
Minor
BAT
None
BID
Bay Interface ID Conflict
Major
CTLR
CTLR
BTA
Battery Test Active
RO
BD
BD
BTJ
Battery Thermal Major
Major
BAT
None
BTN
Battery Thermal Minor
Minor
BAT
None
CCH
Configuration Changed
RO
None
None
CDFA
Converter Distribution Fuse
Major
RECT
MJF
CDID
Converter ID Conflict
Major
RECT
None
CFA
Converter Fail
Minor
RECT
None
CLC
Clock Changed
RO
None
None
CMA
Minor Communications Failure Minor
CTLR
None
CMFA
Multiple Converter Fail
Major
RECT
None
CNF1
Contactor 1 Failed
Major
BAT
None
CNF2
Contactor 2 Failed
Major
BAT
None
CNF3
Contactor 3 Failed
Major
BAT
None
CNO1
Contactor 1 Open
Major
BAT
None
CNO2
Contactor 2 Open
Major
BAT
None
CNO3
Contactor 3 Open
Major
BAT
None
COF
Queue Overflow
Warning
None
None
COR
Number Did Not Respond
Warning
None
None
CPA
Circuit Pack Fail
Major
CTLR
CTLR
CRA
Controller Fail
Major
CTLR
CTLR
DID
Rectifier ID Conflict
Major
RECT
None
EMD
Energy Management Disabled Warning
None
None
EPD
Excess Plant Drain
Minor
RECT
None
EPO
Emergency Power Off
Critical
BATT
None
EPR
External Password Reset
Warning
None
None
ETO
Engine Transfer Timeout
Minor
AC
None
EXL
Excessive Login Attempts
Warning
None
None
FAJ
External Fuse Major
Major
DIST
MJF
FAN
External Fuse Minor
Minor
DIST
MNF
HCL
History Cleared
RO
None
None