GE Industrial Solutions DV-300 DC Quick Start User Manual
Page 31

DV-300 Adjustable Speed Drives
—————— Quick Start up guide ——————
QS
31
Message
Possible causes
Hints
Enable seq error enable input circuit, TB 12, is closed
the enable input can not be tied to +24 V with
before the drive is finished powering up.
parameter [main commands = terminals] while the
drive powers up. This is to prevent unintentional
automatic restarting.
External fault
external fault circuit, TB point 15, is
control circuit is open
open circuit, not tied to +24 V
blown 24 V fuse
Overcurrent
overcurrent setting is too low
check parameter [ overcurrent thr ]
current regulator is mistuned
check Eint and regulator tuning
short circuit or ground fault in armature circuit
check motor circuit integrity
Field loss
no field current
blown fuse in field package AC input
field current parameters are wrong
open field circuit
field current below min field settings
check min field setting, field weakening
parameters
unstable flux regulator, check output current
stability and parameters [Flux P], [Flux I ],
[voltage P gain], [voltage I gain]
Speed fbk loss
loss of encoder input
check encoder power supplies, connections, and
wiring
check encoder jumper settings
misadjustment of encoder loss detection
misadjustment of [enable fbk contrl] parameters
Opt2 failure
DGF card failure
Option 2 is enabled with the DGF card ribbon
cable disconnected. Card is failed
DGF software error
A software error has occurred, for instance, a
divide by zero error.
Improper DGF card parameter settings have been
entered.
Reset the DGF card using jumper S17, also trying
cycling power.
Bus loss
Problem with the bus wiring
check wiring, termination resistors, etc...
excessive noise on the bus
check wiring, grounding practices
improper bus configuration
check bus info, data size, data type, addressing,
configuration data
replace card
Opt 1 failure
bad option 1 card
replace card