GE Industrial Solutions DV-300 DC Quick Start User Manual
Page 16

GEH-6129
—————— Quick Start up guide ——————
QS
16
Press the down arrow to go to the next parameter.
Motor data
Full load current
Press ENT
Enter the nameplate armature amps as recorded
in section 3d. . press ENT
Press the down arrow to go to the next parameter.
Motor data
Motor max speed
Press ENT
Enter the same rpm as entered for speed base value(
rated motor rpm recorded from section 3 d.,
corresponding to the maximum desired motor rpm
), press ENT
Press the down arrow to go to the next parameter.
Motor data
Max output volts
Default = 500 VDC press ENT to change
Enter the nameplate output volts as recorded from
section 3 d, if different from default, press ENT
Press CANC to return to Motor data menu, and press
the down arrow to go to the next parameter menu.
START UP
Limits
The default settings for these are adequate for most
applications @ 500 VDC and 150% OL for 1 minute.
The list below shows some possible applications re-
quiring user changes to “Limits” parameters:
-
For weak field operations:
If
top speed field current
speed field current
base
< .7
then “START UP \ Limits \ Flux current min “
will
need adjusted
-
230 VAC operation - also change [prog alarms
\ undervoltage threshold] , and Motor data ....
-
Overload capacities different than 150% for 60
seconds, [Overload contr] and [ T curr limit]
Press the down arrow to go to the next parameter menu.
START UP
Speed feed-back
Press ENT
Speed feed-back
Speed feed-back sel
Press ENT
Use the + arrow to select speed feedback type =
armature, press ENT
Press CANC to return to
START UP
Speed feed-back
the default settings are already set for speed control
using a potentiometer wired to analog input, skip to
SAVE PARAMETERS.
For keypad control of speed reference, go to menu
selection.
START UP
Analog inputs
Press ENT
Analog inputs
Analog input 1
Press ENT
Analog inputs
Analog input 1 sel
Press ENT
Hold in the - key until entry shows OFF,