DV-300 Adjustable Speed Drives
—————— Quick Start up guide ——————
QS
13
3f. Regulation card jumper settings
Jumper settings to use 6KCV300PIU PC Interface Unit - ( RS232 isolator )
Jumpers S18 & S19 = B, Jumper S29 & S30 = ON Jumper S15 = Off
or the 6KCV300CTI PC configurator Interface Unit - ( RS232/RS485 )
Jumpers S18 & S19 = B, Jumper S29 & S30 = On Jumper S15 = On
Jumper Factory
Description
Record
default
settings:
S4
Matching of the input voltage of the tachogenerator reaction, see table 4.4.3 (User manual)
Speed feedback channel selection
A = Enc 1 speed feedback channel
( XE1 connector with sinusoidal encoder, or digital encoder with 6KCV300DES )
B = analog tachometer
for digital encoder into XE2, or armature feedback (tachless) this jumper position has no effect
Analog input 1 setup
Off = 0-10 V/ -10 V to + 10 V input
ON = 4-20mA/0-20mA input
Analog input 2 setup
Off = 0-10 V/ -10 V to + 10 V input
ON = 4-20mA/0-20mA input
Analog input 3 setup
Off = 0-10 V/ -10 V to + 10 V input
ON = 4-20mA/0-20mA input
RS 485 programming port (XS) termination resistors
Off - no termination resistors
ON - termination resistors in
S15
On
Adaptation of the regulation card to the device type, see table 4.4.2 (User manual)
Selection of the internal/external supply of the RS485 serial interface
OFF - Serial interface supplied from the outside (PIN 5 and 9) and galvanic divided form the
regulation section.
ON - Serial interface supplied from the inside and connected to the potential reference point of the
regulation. PIN 5 and 9 are used to supply the adaptor of the serial interface (for use of
6KDV300PIU).
Encoder 2 input (XE2) marker channel ( also called index , or C channel) input
Off - marker channel (also called index , or C channel) input not used
ON - marker channel (also called index , or C channel) input monitored
Encoder 2 input (XE2) A, /A, B, /B voltage
Off - 15 ... 30 V
ON - 5 V
Tqs350
ON Mounted Jumpers
OFF Non mounted Jumpers
S21,S22,
S23
Off
S18,S19
B
S20
Off
S12,S13
Off
S10
Off
S11
Off
S5,S6
B
S9
Off
N
OTE
!
For sizes 6KDV3280... (American P/N) 6KDV3350... (European P/N) and higher, 115 VAC operation
requires a jumper between terminals SA & SB. These points are located on a terminal board on the top
of the converter module.