GEH-6129
—————— Quick Start up guide ——————
QS
12
Table 3e1: DV-300 Rev 7.1 or greater, field current calibration resistor dipswitch settings for
model numbers 6KDV3017...-3850, (European model numbers 6KDV3020..-310H)
Resistance = 1667 / field current amps
Switch ohms
168.5 ohm
333 ohm
182 ohm
36.4 ohm
845 ohm
1668 ohm
Field curr scale
S14-1
S14-2
S14-3
S14-4
S14-5
S14-6
S14-7
S14-8
1.0 A
OFF
OFF
OFF
OFF
OFF
ON
1685 ohm
2.0 A
OFF
OFF
OFF
OFF
ON
OFF
845 ohm
3.0 A
OFF
OFF
OFF
OFF
ON
ON
558.8 ohm
5.0 A
OFF
ON
OFF
OFF
OFF
OFF
333 ohm
10.0 A
ON
OFF
OFF
OFF
OFF
OFF
168.5 ohm
12.9 A
ON
OFF
OFF
OFF
ON
ON
129.2 ohm
17.2 A
OFF
ON
ON
OFF
ON
ON
97 ohm
20.0 A
ON
OFF
ON
OFF
OFF
ON
83 ohm
24.1 A
ON
ON
ON
OFF
OFF
OFF
69 ohm
DV0032g
Equivalent
resistance
Not used
1=dipswitch in ON position
Table 3e2: DV-300 Rev 7.1 or greater, field current calibration resistor dipswitch settings for
model numbers 6KDV30900...-31500, (European model numbers 6KDV31200..-32000)
Resistance = 3332 / field current amps
Field current scale S14-1
S14-2
S14-3
S14-4
S14-5
S14-6
Equivalent resistance
40A
ON
OFF
ON
OFF
OFF
OFF
83 W
20A
ON
OFF
OFF
OFF
OFF
OFF
168 W
10A
OFF
ON
OFF
OFF
OFF
OFF
332 W
1=dipswitch in ON position
Tqs330
Table 3e3 : DV-300 Rev 7.1 or greater, field current calibration resistor dipswitch settings for
model numbers 6KDV31800...-32350, (European model numbers 6KDV32400..-33300)
Resistance = 1667 / field current amps
Field current scale S14-1
S14-2
S14-3
S14-4
S14-5
S14-6
Equivalent resistance
70A
ON
OFF
ON
ON
OFF
OFF
23.8 W
46A
OFF
OFF
OFF
ON
OFF
OFF
36.4 W
24A
ON
ON
ON
OFF
OFF
OFF
69.2 W
14A
OFF
ON
ON
OFF
OFF
OFF
117.6 W
1=dipswitch in ON position
Tqs340
Setting all dipswitch settings to 0 (OFF) allows a custom calculated resistor to be used in terminals LA and LB,
on the regulation board, using the formulas listed above.