3d. motor data tabulation
Before commissioning, it is recommended to record the actual motor nameplate data. Also record gearbox, and
attached roll diameter, or any appropriate mechanical data that may be needed during setup.
This table may be used as a guide to record motor nameplate and application data
Typical DC Motor Nameplate
HP (kW)
RPM
Volts
Arm Amps
Fld Amps
Fld ohms 25 C
Fld is an abbreviation for field
Gear in speed
· :
rpm
· gear in speed is the top motor rpm to achieve rated machine speed
Acceleration time · :
seconds
· :
seconds
: constant current, (fixed field current)
field weakening (see example below)
: analog
V /
RPM
digital tacho into Encoder 2
PR
None
P
(circle one)
(circle one)
tachometer type
and calibration
see jumpers in 3.f.
see jumpers in 3.f.
see jumpers note in 3.f.
Deceleration time
Field control
Nameplate dual speed rating
The value for RPM may be represented with two values, the first representing base speed , which is the rpm at
nameplate volts and nameplate field current.
A second RPM value, if shown, corresponds to rated top speed, which is achieved at rated nameplate volts, and
a weak field setting. The weak field setting would correspond to the second value of field amps.
For the nameplate below, base speed is 1750 rpm @ 3 amps field and top speed is 2300 rpm @ 1 amp field
Typical DC Motor Nameplate
HP (kW)
20
RPM
1750 / 2300
Volts 500
Arm Amps 32
Fld Amps
3.0 / 1.0
Fld ohms 25 C
72
Verify the motor data matches the drive power rating, output voltages, and required motor speed is achievable.
If files in the GE Control System Toolbox were predefined off-line, verify the entered data is correct before
downloading to the drive