Appendix C: Operation without a Controller -
Alarm Wiring
Each converter shelf provides alarm contact closures for Power Major and Power Minor independently of a controller.
Wire these relays into the alarm network in deployments where a controller is not utilized. When a controller is installed
then an alarm cable can be attached to the controller – see the Connect Office Alarms section.
Step
Action
1.
Attach the required alarm leads to the office alarm screw terminals (TB1 on the alarm card) as
designated.
Figure 34 Office Alarm Pin Outs - Alarm Cards
2.
Reinstall Alarm card and close distribution door.
Converter Shelf Alarm Card State Table
This section shows Alarm and LED response for the Alarm Card LEDs and Relays:
The Converter Shelf contains a pair of A bus feeds and a pair of B bus feeds. The use of dual A and B feeds is to not
exceed the 48 AMPS L2 input current per feed. The A bus feeds are designated A
1-6
and A
9-12
, and power shelf slots 1-6
(left side) and 7-12 (right side) respectively. The B bus feeds are also designated in an identical fashion. The alarm card
monitors the -48v on each of these four feeds, and asserts alarms and indicators - Table 11.
Table 11 Converter Shelf Alarm Card States
-48 V Input Bus
Vin LEDs
Status LEDs
Alarm Relays
A
1-6
B
1-6
A
7-12
B
7-12
A LED
B LED
OK LED
ALM LED
PMN
PMJ
1
OK
OK
OK
OK
GRN
GRN
GRN
OFF
E
E
2
LOW
OK
OK
OK
RED
GRN
OFF
YEL
D
E
3
OK
LOW
OK
OK
GRN
RED
OFF
YEL
D
E
4
OK
OK
LOW
OK
RED
GRN
OFF
YEL
D
E
5
OK
OK
OK
LOW
GRN
RED
OFF
YEL
D
E
6
LOW
LOW
OK
OK
RED
RED
OFF
RED
E
D
7
LOW
OK
LOW
OK
RED
GRN
OFF
RED
E
D
8
LOW
OK
OK
LOW
RED
RED
OFF
RED
E
D
9
OK
LOW
LOW
OK
RED
RED
OFF
RED
E
D
10
OK
LOW
OK
LOW
GRN
RED
OFF
RED
E
D
11
OK
OK
LOW
LOW
RED
RED
OFF
RED
E
D
12
LOW
LOW
LOW
OK
RED
RED
OFF
RED
E
D
13
LOW
LOW
OK
LOW
RED
RED
OFF
RED
E
D
14
LOW
OK
LOW
LOW
RED
RED
OFF
RED
E
D
15
OK
LOW
LOW
LOW
RED
RED
OFF
RED
E
D
16
LOW
LOW
LOW
LOW
OFF
OFF
OFF
OFF
D
D
17
E – Energized relay in non-alarm state; D – De-energized relay in alarm state