Troubleshooting, System, Table 1 system troubleshooting – GE Industrial Solutions CPS2400U User Manual
Page 25
CPS2400U Upstream System – 19” Product Manual
CPS2400U
850028186 r04 December 2013
25
Troubleshooting
Only Remote Power System specific alarms are included in this section. See Galaxy Pulsar Edge Product Manual for details of other controller alarms.
Many alarms are best processed at the converter shelf alarm card and converter card level.
LAN port or Craft port access provides additional information – see Galaxy Pulsar Edge Product Manual for details
System
Table 1 System Troubleshooting
Controller
Alarm Card
Converter Card
Possible Problem
Possible Solution
Alarm Display
Back-
light
Relay
State
Alarm
LED
State
Relay
State
OK
LED
State
Alarm
LED
State
Normal
Green
Green
none
Various
Yellow
or Red
Green
Green
Latched Controller Alarm
or Alarm for Removed
Equipment
Execute Controller commands “Clear Events” and
“Uninstall Equipment”.
Controller – Control/Operations
Web Pages – Maintenance tab.
Circuit Fail
Yellow
Min
Yellow
Min
Green
Flashing
Yellow
Short + to -
Make sure each converter has an independent
isolated send and return path.
Circuit Fail
Yellow
Min
Yellow
Min
Flashing
Red
Flashing
Red
Short to Ground
Make sure each converter has an independent
isolated send and return path.
Communication
Fail
Yellow
Min
Yellow
Min
Green
Off
1 Card Removed
Check to see that all cards are seated.
Replace non-functioning cards.
Communication
Fail
Red
Maj
2 Cards Removed
Check to see that all cards are seated.
Replace non-functioning cards.
Communication
Fail
Red
Maj
Flashing
Red
Green
Off
Communication Cable
Removed
Check communication path from alarm cards to
Controller.
If controller is not present, set alarm card rotary
switch to Shelf ID 0,0 for contact closures only
communication.
Communication
Fail
Red
Maj
Green
Flashing
Red
Alarm Card Removed
Replace Alarm card.
None
Green
Green
Yellow
Standby
Remove unit from standby if desired using
Controller or web page interface
Circuit Fail
Yellow
Min
Yellow
Min
Green
Flashing
Yellow
Open Fuse
Replace Converter.
Note: Replacing a Converter storing will interrupt
service to the other line served by the Converter.