Alarm card alarm states, Table 3 alarm card state leds and relays – GE Industrial Solutions CPS2400U User Manual
Page 28
CPS2400U Upstream System – 19” Product Manual
CPS2400U
850028186 r04 December 2013
28
Table 3 Alarm Card State LEDs and Relays
Alarm States
LEDs
Relays
Converter
State
-48 V Feed
State
Fan Shelf
State
OK LED
ALM LED
PMN
PMJ
OK
OK
OK
Green
Minor
OK or Minor
OK or Minor
Amber
PMN
OK or Minor
Minor
OK or Minor
Amber
PMN
OK or Minor
OK or Minor
Minor
Amber
PMN
Major
any
any
Red
PMJ
any
Major
any
Red
PMJ
any
any
Major
Red
PMJ
any
Unpowered
any
PMN PMJ
Alarm Card Alarm States
Alarm states are ranked from low severity to high severity.
Alarm State
Severity
Major or PMJ ....................... Highest
Minor or PMN ...................... Medium
None or OK .............. Lowest (no alarm)
Alarm states are aggregated and combined into successively larger representations:
Converter circuit states are aggregated into a Converter Card state.
Converter Card states and -48V Input Feed states are aggregated and combined into a Converter Shelf state.
Converter Shelf states and Fan Shelf states are aggregated and combined into a Converter system state.
• System Alarm State - the highest alarm state within the system, including Converter Shelves and Fan Shelves.
• Shelf Alarm State - the highest alarm state within the shelf, including Converter Cards and -48V Input Feeds,
Fan Shelf state (if wired), and Alarm Card I
2
C to RS-485 communication processor.
OK
No alarms are active – all OK
PMN
Minor alarms only are active
PMJ
Major – at least one major alarm is active
• Fan Shelf Alarm State – the alarm state of the connected Fan Shelves.
Each Fan Shelf has a single alarm that is active when one or more fans have failed or when Fan Shelf DC
voltage is low.
OK
No Fan Shelves have alarms are active – all OK
Minor One Fan Shelf has alarm active
Major Two Fans Shelves have alarms active
• Converter Card Alarm State - the highest alarm state of all Converter Cards within the shelf
OK
No Converter alarms are active – all OK
Minor at least one Minor Converter alarms only is active
Major at least one Major Converter alarm is active
• -48V Input Feed Alarm State – the alarm state of the four -48V shelf feeds: - Table 2.
OK
None
Minor One input feed Low
Major Multiple input feeds Low
6
Empty cells indicate: OK for inputs, OFF for LEDs, and non-alarm for relays.
7
Alarm relays are energized (powered) in the non-alarm state.
8
The Alarm card is redundantly powered by all four -48V input feeds.