Converter LEDs
Figure 24 Converter LEDs and Test Points
Note: Test points work best if each voltage is measured with respect to ground.
Table 4 Converter LEDs
Action Required
OK LED
Fault LED
Conditions
Notes
None
Green
Off
All OK
Verify circuit
configuration
Off
Yellow
Standby
Standby can be set using the Controller
display or remotely using a web
browser.
Check seating on
Alarm card and
converter card
Green
Blink Red On ½ second,
Off ¼ second
Loss of comm.
Check 5 pin
protectors and faults
to ground
Red Blink
Red Blink
Ground fault
Check output lines
for shorts to each
other
Green
Yellow Blink
Overcurrent or under
voltage
Replace unit
Red Blink
Off
OV or internal failure
Solve Thermal
problem
Off
Red Blink
Thermal Alarm
Latch off after 3 retry cycles
Check source
voltage
Off
Off
card not powered or
input fuse failure
Observe Lamp Test
Bi-Color: 4.5 seconds
on, 4.5 seconds on and
1 second off
Bi-Color: 4.5 seconds
on, 4.5 seconds on and
1 second off
Lamps test requested
from controller
Display Examples
LED Display
Conditions
Action Required
All OK
None
Circuit Placed in Standby
None depending on desired state of the circuit
Standby state can be set using the controller or
web browser.
9
Examples in the table are shown for conditions on the B circuit of the QS982A card. The same Conditions and Actions
apply for the A circuit when A circuit LEDs are illuminated.