beautypg.com

VEGA VVO VEGA Visual Operating User Manual

Page 18

background image

18

VEGA Visual Operating

Set-up of a VBUS-radar sensor VEGAPULS 81F

After the operating range you determine
the measuring conditions. Click to "Sol-
ids“ or "Liquids“ and the options corre-
sponding to your measurement loop.

First of all determine the operating range
of the sensor. Click to "limited“, when the
operating range should be less than the
measuring range of the sensor and enter
in the appropriate fields the min. and max.
distance. With

OK the values will be

saved and you return to the window
"Meas. environment“.

From the window "Meas. environment“ you
reach further windows. Proceed in the de-
scribed sequence.

Often many different echoes are caused with
the radar measurement, which often cannot
be clearly detected as useful signal by the
processing electronics. In this case you can
choose a distance and inform the sensor that
this is the actual distance.