Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

E50C2 FDS

E50C3 L

og

E50xx REG.

R/W NV Format

Units

Scale

Range

Description

• 169

R/W NV UInt

1-42, 146,
155-157,
257-336

Log Register Pointer 1 –
Default is 1 (Real Energy MSR)

Log Register Selection – Write the number of the 16 bit register to be logged.

To log a 32 bit value (such as accumulators and floating point values) two log

registers must be used, one each for the most and least significant register

(MSR & LSR).

• 170

R/W NV UInt

Log Register Pointer 2 –
Default is 2 (Real Energy LSR)

• 171

R/W NV UInt

Log Register Pointer 3 –
Default is 29 (Reactive Energy

MSR)

• 172

R/W NV UInt

Log Register Pointer 4 –
Default is 30 (Reactive Energy

LSR)

• 173

R/W NV UInt

Log Register Pointer 5 –
Default is 37 (Real Demand)

• 174

R/W NV UInt

Log Register Pointer 6 –
Default is 38 (Reactive Demand)

• 175

R/W NV UInt

Log Register Pointer 7 –
Default is 39 (Apparent Demand)

• 176

R/W NV UInt

Log Register Pointer 8 –
Default is 155 (Month/Day)

• 177

R/W NV UInt

Log Register Pointer 9 –
Default is 156 (Year/Hour)

• 178

R/W NV UInt

Log Register Pointer 10 –
Default is 157 (Minutes/Seconds)

Floating Point Data

• 257/258 R

NV Float

kWh

Real Energy Consumption (clear via reset register)

• 259/260 R

NV Float

kWh

Real Energy Consumption (clear via reset register)

• 261/262 R

Float

kW

Total Instantaneous Real Power

• 263/264 R

Float

kVAR

Total Instantaneous Reactive Power

• 265/266 R

Float

kVA

Total Instantaneous Apparent Power

• 267/268 R

Float

Ratio

0.0-1.0

Total Power Factor (Total KW / Total KVA)

• 269/270 R

Float

Volt

Voltage, L-L, Average of 3 Phases

• 271/272 R

Float

Volt

Voltage, L-N, Average of 3 Phases

• 273/274 R

Float

Amp

Current, Average of 3 Phases

• 275/276 R

Float

kW

Real Power, Phase A

• 277/278 R

Float

kW

Real Power, Phase B

• 279/280 R

Float

kW

Real Power, Phase C

• 281/282 R

Float

Ratio

0.0-1.0

Power Factor, Phase A

• 283/284 R

Float

Ratio

0.0-1.0

Power Factor, Phase B

• 285/286 R

Float

Ratio

0.0-1.0

Power Factor, Phase C

• 287/288 R

Float

Volt

Voltage, Phase A-B

• 289/290 R

Float

Volt

Voltage, Phase B-C

• 291/292 R

Float

Volt

Voltage, Phase A-C

• 293/294 R

Float

Volt

Voltage, Phase A-N

• 295/296 R

Float

Volt

Voltage, Phase B-N

• 297/298 R

Float

Volt

Voltage, Phase C-N

• 299/300 R

Float

Amp

Current, Instantaneous, Phase A

• 301/302 R

Float

Amp

Current, Instantaneous, Phase B

• 303/304 R

Float

Amp

Current, Instantaneous, Phase C

• 305/306 R

Float

Reserved, returns 0x7FC00000 (QNAN)

• 307/308 R

Float

Hz

45.0-65.0

Frequency (derived from Phase A)

• 309/310 R

NV Float

kVAh

Apparent Energy Consumption

Modbus Point Map (cont.)