Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

Quick Setup
Instructions

These instructions assume the meter is set to factory defaults. If it has been previously configured, all optional values should be
checked.

1. Press the

+

+

or

button repeatedly until SETUP screen appears.

2. to the PASWD screen.

3. through the digits. Use the

+

+

or

buttons to select the password (the default is 00000). Exit the screen to the right.

4. Use the

+

+

or

buttons to select the parameter to configure.

5. If the unit has an RS-485 interface, the first Setup screen is S COM (set communications).

a. to the ADDR screen and through the address digits. Use the

+

+

or

buttons to select the Modbus address.

b. to the BAUD screen. Use the

+

+

or

buttons to select the baud rate.

c. to the PAR screen. Use the

+

+

or

buttons to select the parity.

d. back to the S COM screen.

6.

to the S CT (Set Current Transducer) screen. If this unit does not have an RS-485 port, this will be the first screen.

a. to the CT V screen. Use the

+

+

or

buttons to select the voltage mode Current Transducer output voltage.

b. to the CT SZ screen and through the digits. Use the

+

+

or

buttons to select the CT size in amps.

c. back to the S CT screen.

7.

to the S SYS (Set System) screen.

a. to the SYSTM screen. Use the

+

+

or

buttons to select the System Type (see wiring diagrams).

b. back to the S SYS screen.

8. (Optional)

to the S PT (Set Potential Transformer) screen. If PTs are not used, then skip this step.

a. to the RATIO screen and through the digits. Use the

+

+

or

buttons to select the Potential Transformer step down

ratio.

b. back to the S PT screen.

9.

to the S V (Set System Voltage) screen.

a. to the VLL (or VLN if system is 1L-1n) screen and through the digits. Use the

+

+

or

buttons to select the Line to Line

System Voltage.

b. back to the S V screen.

10. Use the to exit the setup screen and then SETUP.

11. Check that the wrench is not displayed on the LCD.

a. If the wrench is displayed, use the

+

+

or

buttons to find the ALERT screen.

b. through the screens to see which alert is on.

For full setup instructions, see the configuration instructions on the following pages.