Modbus point map – Veris Industries E50C3 Install User Manual
Page 19

ZL0103-0B
Page 19 of 26
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50B1, E50C2, E50C3
TM
Modbus Point Map
E50C2 FDS
E50C3 L
og
E50xx REG.
R/W NV Format
Units
Scale
Range
Description
Integer Data
•
• 001
R
NV ULong
kWh
E
0-0xFFFF
Real Energy Consumption (MSR)
Clear via reset register
•
• 002
0-0xFFFF
Real Energy Consumption (LSR)
•
• 003
R
UInt
kW
W
0-32767
Total Instantaneous Real Power (3 Phase Total)
•
• 004
R
UInt
kVAR
W
0-32767
Total Instantaneous Reactive Power (3 Phase Total)
•
• 005
R
UInt
kVA
W
0-32767
Total Instantaneous Apparent Power (3 Phase Total)
•
• 006
R
UInt
Ratio
0.0001
0-10000
Total Power Factor (Total KW / Total KVA)
•
• 007
R
UInt
Volt
V
0-32767
Voltage, L-L, Average of 3 Phases
•
• 008
R
UInt
Volt
V
0-32767
Voltage, L-N, Average of 3 Phases
•
• 009
R
UInt
Amp
I
0-32767
Current, Average of 3 Phases
•
• 010
R
UInt
kW
W
0-32767
Real Power, Phase A
•
• 011
R
UInt
kW
W
0-32767
Real Power, Phase B
•
• 012
R
UInt
kW
W
0-32767
Real Power, Phase C
•
• 013
R
UInt
Ratio
0.0001
0-10000
Power Factor, Phase A
•
• 014
R
UInt
Ratio
0.0001
0-10000
Power Factor, Phase B
•
• 015
R
UInt
Ratio
0.0001
0-10000
Power Factor, Phase C
•
• 016
R
UInt
Volt
V
0-32767
Voltage, Phase A-B
•
• 017
R
UInt
Volt
V
0-32767
Voltage, Phase B-C
•
• 018
R
UInt
Volt
V
0-32767
Voltage, Phase A-C
•
• 019
R
UInt
Volt
V
0-32767
Voltage, Phase A-N
•
• 020
R
UInt
Volt
V
0-32767
Voltage, Phase B-N
•
• 021
R
UInt
Volt
V
0-32767
Voltage, Phase C-N
•
• 022
R
UInt
Amp
I
0-32767
Current, Instantaneous, Phase A
•
• 023
R
UInt
Amp
I
0-32767
Current, Instantaneous, Phase B
•
• 024
R
UInt
Amp
I
0-32767
Current, Instantaneous, Phase C
•
• 025
R
UInt
Reserved; returns 0x8000 (QNAN)
•
• 026
R
UInt
Hz
0.01
4500-6500
Frequency (derived from Phase A)
•
• 027
R
NV ULong
KVAh
E
0-0xFFFF
Apparent Energy Consumption (MSR)
Clear via reset register
•
• 028
0-0xFFFF
Apparent Energy Consumption (LSR)
•
• 029
R
NV ULong
KVARh
E
0-0xFFFF
Reactive Energy Consumption (MSR)
Clear via reset register
•
• 030
0-0xFFFF
Reactive Energy Consumption (LSR)
•
• 031
R
UInt
kVA
W
0-32767
Apparent Power, Phase A
•
• 032
R
UInt
kVA
W
0-32767
Apparent Power, Phase B
•
• 033
R
UInt
kVA
W
0-32767
Apparent Power, Phase C
•
• 034
R
UInt
kVAR
W
0-32767
Reactive Power, Phase A
•
• 035
R
UInt
kVAR
W
0-32767
Reactive Power, Phase B
•
• 036
R
UInt
kVAR
W
0-32767
Reactive Power, Phase C
•
• 037
R
UInt
kW
W
0-32767
Total Real Power Present Demand
•
• 038
R
UInt
kVAR
W
0-32767
Total Reactive Power Present Demand
•
• 039
R
UInt
kVA
W
0-32767
Total Apparent Power Present Demand
•
• 040
R
NV UInt
kW
W
0-32767
Total Real Power Max Demand
•
• 041
R
NV UInt
kVAR
W
0-32767
Total Reactive Power Max Demand
•
• 042
R
NV UInt
kVA
W
0-32767
Total Apparent Power Max Demand