beautypg.com

Modbus point map (cont.) – Veris Industries E50C3 Install User Manual

Page 21

background image

ZL0103-0B

Page 21 of 26

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

E50C2 FDS

E50C3 L

og

E50xx REG.

R/W NV Format

Units

Scale

Range

Description

• 138

R

SInt

-4 0.0001
-3 0.001
-2 0.01
-1 0.1
0 1.0
1 10.0
2 100.0
3 1000.0
4 10000.0

Scale Factor I (Current)

Scale Factors

Note: These registers contain a signed

integer, which scales the corresponding

integer registers. Floating point registers

are not scaled. Scaling is recalculated

when the meter configuration is changed.

• 139

R

SInt

Scale Factor V (Voltage)

• 140

R

SInt

Scale Factor W (Power)

• 141

R

SInt

Scale Factor E (Energy)

• 142

R/W NV UInt

%

1-99

Phase Loss Voltage Threshold in percent of system voltage (register

134). Default is 10 (%). Any phase (as configured in register 130)

that drops below this threshold triggers a Phase Loss alert - i.e.

if the System voltage is set to 480 V L-L, the L-N voltage for each

phase should be 277 V. When the threshold is set to 10%, if any

phase drops more than 10% below 277 V, (less than 249 V), or

if any L-L voltage drops more than 10% below 480 V (less than

432 V) the corresponding phase loss alarm bit in register 146 will

be true.

Phase Loss Output

Note: The phases tested are determined by

the System Type.

• 143

R/W NV UInt

%

1-99

Phase Loss Imbalance Threshold in Percent. Default is 25% phase

to phase difference. For a 3-phase Y (3 + N) system type (40 in

register 130), both Line to Neutral and Line to Line voltages are

tested. In a 3-phase Δ System type (31 in register 130), only Line

to Line voltages are examined. In a single split-phase (2 + N)

system type (12 in register 130), just the line to neutral voltage

are compared.

• 144

R/W NV UInt

Wh

10000,
1000,
100,
10

Wh (& VARh, if equipped with

FDS) Energy per Pulse Output

Contact Closure. If the meter

cannot find a pulse duration

that will keep up with the max.

system power (register 135), it

will reject the new value. Try a

larger value.

kWh Pulse Contacts

Note: The kWh pulse contact can keep up with a maximum power (Watts) of

1800000 x Wh pulse weight ÷ contact closure duration (in mses)

• 145

R

NV UInt

ms

500,
250,
100,
50,
25,
10

Pulse Contact Closure Duration

in msec. Read-only. Set to the

slowest duration that will keep

up with the theoretical max.

system power (register 135).

The open time ≥ the closure

time, so the max. pulse rate

(pulses per sec) is the inverse of

double the pulse time.

Modbus Point Map (cont.)