Installation Guide

Power Monitoring

E50B1, E50C2, E50C3

TM

E50C2 FDS

E50C3 L

og

E50xx REG.

R/W NV Format

Units

Scale

Range

Description

• 146

R

UInt

Diagnostic Alert Bitmap. 1 = Active:
Bit 0: Phase A Voltage out of range
Bit 1: Phase B Voltage out of range
Bit 2: Phase C Voltage out of range
Bit 3: Phase A Current out of range
Bit 4: Phase B Current out of range
Bit 5: Phase C Current out of range
Bit 6: Frequency out of the range of 45 – 65 Hz OR there is insufficient voltage to determine frequency.
Bit 7: Reserved for future use
Bit 8: Phase Loss A
Bit 9: Phase Loss B
Bit 10: Phase Loss C
Bit 11: Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases
Bit 12: Low Power Factor on B
Bit 13: Low Power Factor on C
Bit 14: Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power

(registers 3 and 261/262). To fix, increase the pulse energy register (register 144) and reset the energy

accumulators (see reset register 129).

Bit 15: Energy pulse output configuration error (present pulse energy setting may not keep up with the

theoretical max. system power; see register 135). To fix, increase the pulse energy (register 144).

• 147

R

NV UInt

0-32767

Count of Energy Accumulator resets

• 148

R

UInt

Reserved (returns 0)

• 149

R/W NV UInt

1-6

Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that

make a single demand interval. For block demand, set this to 1.

Demand Calculation

• 150

R/W NV UInt

Seconds

0, 10-32767

Sub-Interval Length in seconds. For sync-to-comms, set this to 0 and use the reset

register (129) to externally re-start the sub-interval. On the E50C3, this is also the

logging interval.

• 151

R/W

UInt

1-32767

Reserved (returns 0)

• 152

R/W NV UInt

0-32767

Power Up Counter.

• 153

R

NV UInt

0-32767

Output Configuration. E50B1, E50C2, and E50C3 units have a NO (normally open) energy contact and NC

(normally closed) (Normally Open - Form A or Normally Closed - Form B) Phase Loss contact. While the relay

used for the Phase Loss contact is Normally Closed (contacts are closed when the meter is not powered),

closure indicates the presence of an alarm; either loss of phase, when the meter is powered, or loss of power

when the meter is not. The contacts are open when the meter is powered and no phase alarm conditions are

present.

3rd Output:
0 = RS-485
2 = VAR Pulse

• 154

R

UInt

Reserved, returns 0

Logging Configuration and Status

• 155

R/W NV UInt

Day /

Month

See Bytes

Most Significant Byte (MSB)

Least Significant Byte (LSB)

Date / Time Clock. Following a power cycle,

resets to:

Day 01 Month 01
Hour 00 Year (20) 00

Day 1-31 (0x01-0x1F)

Month 1-12 (0x01-0x0C)

• 156

R/W NV UInt

Hour /

Year

See Bytes

Hour 0-23 (0x00-0x17)

Year 0-199 (0x00-0xC7)

• 157

R/W NV UInt

Seconds /

Minutes

See Bytes

Seconds 0-59 (0x00-0x3B)

Minutes 0-59 (0x00-0x3B)

Modbus Point Map (cont.)