Modbus point map (cont.) – Veris Industries E50C3 Install User Manual
Page 22

ZL0103-0B
Page 22 of 26
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50B1, E50C2, E50C3
TM
E50C2 FDS
E50C3 L
og
E50xx REG.
R/W NV Format
Units
Scale
Range
Description
•
• 146
R
UInt
Diagnostic Alert Bitmap. 1 = Active:
Bit 0: Phase A Voltage out of range
Bit 1: Phase B Voltage out of range
Bit 2: Phase C Voltage out of range
Bit 3: Phase A Current out of range
Bit 4: Phase B Current out of range
Bit 5: Phase C Current out of range
Bit 6: Frequency out of the range of 45 – 65 Hz OR there is insufficient voltage to determine frequency.
Bit 7: Reserved for future use
Bit 8: Phase Loss A
Bit 9: Phase Loss B
Bit 10: Phase Loss C
Bit 11: Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases
Bit 12: Low Power Factor on B
Bit 13: Low Power Factor on C
Bit 14: Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power
(registers 3 and 261/262). To fix, increase the pulse energy register (register 144) and reset the energy
accumulators (see reset register 129).
Bit 15: Energy pulse output configuration error (present pulse energy setting may not keep up with the
theoretical max. system power; see register 135). To fix, increase the pulse energy (register 144).
•
• 147
R
NV UInt
0-32767
Count of Energy Accumulator resets
•
• 148
R
UInt
Reserved (returns 0)
•
• 149
R/W NV UInt
1-6
Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that
make a single demand interval. For block demand, set this to 1.
Demand Calculation
•
• 150
R/W NV UInt
Seconds
0, 10-32767
Sub-Interval Length in seconds. For sync-to-comms, set this to 0 and use the reset
register (129) to externally re-start the sub-interval. On the E50C3, this is also the
logging interval.
•
• 151
R/W
UInt
1-32767
Reserved (returns 0)
•
• 152
R/W NV UInt
0-32767
Power Up Counter.
•
• 153
R
NV UInt
0-32767
Output Configuration. E50B1, E50C2, and E50C3 units have a NO (normally open) energy contact and NC
(normally closed) (Normally Open - Form A or Normally Closed - Form B) Phase Loss contact. While the relay
used for the Phase Loss contact is Normally Closed (contacts are closed when the meter is not powered),
closure indicates the presence of an alarm; either loss of phase, when the meter is powered, or loss of power
when the meter is not. The contacts are open when the meter is powered and no phase alarm conditions are
present.
3rd Output:
0 = RS-485
2 = VAR Pulse
•
• 154
R
UInt
Reserved, returns 0
Logging Configuration and Status
• 155
R/W NV UInt
Day /
Month
See Bytes
Most Significant Byte (MSB)
Least Significant Byte (LSB)
Date / Time Clock. Following a power cycle,
resets to:
Day 01 Month 01
Hour 00 Year (20) 00
Day 1-31 (0x01-0x1F)
Month 1-12 (0x01-0x0C)
• 156
R/W NV UInt
Hour /
Year
See Bytes
Hour 0-23 (0x00-0x17)
Year 0-199 (0x00-0xC7)
• 157
R/W NV UInt
Seconds /
Minutes
See Bytes
Seconds 0-59 (0x00-0x3B)
Minutes 0-59 (0x00-0x3B)
Modbus Point Map (cont.)