ElECTRICal INsTallaTION:

Power supply Wiring

The Badger® Data Industrial® Series 3050 requires

12-24 VDC/VAC to operate. Check specifications page

for DC current draw, and AC Volt-Amp requirements. A

fused circuit is always recommended.

Connect the positive of the power supply to the Series

3050 terminal marked (ACL/DC+), and connect the

negative of the power supply to the Series 3050 terminal

marked (ACC/DC-).

If a Badger Data Industrial plug-in power supply (Model

A1026, A-503) is being used connect the black-white wire

to the terminal marked (ACL/DC+) and the Black wire to

the terminal marked (ACC/DC-).

Figure 3 ( Power Supply Wiring)

(+) (-)

12-24VDC

Power

Supply

( Line) (Com)

12-24VAC

Power Supply

OR

Earth

or

Panel

Ground

Ground wire should be heavy gauge and as short as possible