Veris Industries Badger 3050 SERIES Install User Manual
Page 16

16
10:m3/s,
11:m3/min,
12:m3/hr,
13:acreft/s,
14:acreft/min,
15:acreft/hr,
16:bbl/s,
17:bbl/min,
18:bbl/hr,
19:Custom
flow [1-2] rate ndigits = [2-10] -- number of decimal
places to show for flow rate
flow [1-2] rate custom label = [string] -- set the label for
custom units
flow [1-2] rate custom conv = [0-100] -- conversion factor
for custom units
flow [1-2] total units = [0-7] -- set the totalizer units to
display.
0: gal,
1: Mgal,
2: L,
3: ft3,
4: m3,
5: acreft,
6: bbl,
7: Custom
BTU CONFIGURaTION
btu rate units = [0-5] -- set the BTU rate units:
0: kBTU/hr,
1: BTU/min,
2: kW,
3: TR,
4: J/s,
5: Custom
btu rate ndigits = [2-10] -- number of decimal digits to
display
btu rate custom label = [string] -- btu rate custom unit
label
btu rate custom conv = [0-100] -- custom unit conversion
factor
btu total units = [0-6] -- btu totalizer units:
0: BTU,
1: kBTU,
2: MBTU,
3: kWh,
4: MWh,
5: kJ,
6: Custom
btu total ndigits = [2-10] -- number of decimal digits to
display
btu total custom label = [string] -- btu totalizer custom
unit label
btu total custom conv = [0-100] -- custom unit conversion
factor
btu total mode = [0-2] -- totalizer mode:
0: Heating,
1: Cooling,
2: Heating & Cooling
btu sensor type = [0-4] -- temperature sensor type:
0: DI Thermistor,
1: DI RTD,
2: Custom Thermistor,
3: Custom RTD,
4: No sensor
btu sensor correct_k = [0-10] -- correction factor
btu sensor temp_unit = [0-1] -- temperature units to
display
0: deg F
1: deg C
btu sensor t2adj = [-10-10] -- t2a
RElaY OUTPUT CONFIGURaTION
relay [1-5] func = [0-9] -- relay function; relay 5 is the
pulse output
0: Totalizer
1: Alarm
2: Manual Control
relay [1-5] input = [0-8] -- relay input; depends on source
for totalizer:
0: Flow 1 Total
for alarms:
0: Flow 1 Rate
relay [1-5] units = [0-19] -- units on setpoints/rates;
depends on src/input
flow units: same as 'flow [1-2] rate units' above
volume units: same as 'flow [1-2] total units'
relay [1-5] manual = [on/off] -- manually set relay on or
off, if in manual mode
relay [1-5] rate = [x] -- totalizer rate
relay [1-5] ctime = [0-10000] -- pulse width in milliseconds
relay [1-4] latch = [on/off] -- turn on/off relay latching
relay [1-4] setpoint = [x]
relay [1-4] releasepoint = [x]
ANALOG OUTPUT CONFIGURATION
analogout [1-2] func = [0-3]
0: Flow rate
1: BTU rate
2: Temperature
3: PID control
analogout [1-2] src = [0-4]
for flow rate:
0: Flow 1 rate
1: Flow 2 Rate
2: Flow sum
3: Flow 1-2
4: Flow 2-1
for BTU rate: not used
for temperature:
0: Temp 1
1: Temp 2
2: Temp Delta
for PID control:
0: Flow 1 rate
1: Flow 2 rate
analogout [1-2] range = [0-1]
0: 0-20mA