e31

INSTALLATIoN GUIDe

WIrIng

Power must be disconnected and locked out before making any wiring connections.

1. Connect 2-wire or 4-wire Modbus RS-485 daisy chain network (Figures 12 and 13).

Figure 12

Figure 13

SHIELD
RX- TX-
RX+ TX+
TX-
TX+

Master or Slave

SHLD

TX+

TX+

RX+

TX–

TX-

RX-

SHIELD

SHIELD

Master

Slave

SHLD

TX+

TX+

RX+

TX–

TX-

RX-

SHIELD

SHLD

TX+

TX+

RX+

TX–

TX-

RX-

SHIELD

2-Wire

4-Wire

2-Wire Example

Figure 14

+

Belden 1120A or

equivalent

120 Ω terminator

on last device of

daisy chain

Not Used

WARNING: After wiring the RS-485 cable, remove all

scraps of wire or foil shield from the electrical panel.

Wire scraps coming into contact with high voltage

conductors could be DANGEROUS!

2. Mechanically secure the RS-485 cable where it enters the electrical panel.

3. Connect all RS-485 devices in a daisy-chain fashion, and properly terminate the

chain (Figure 14).

4. Shield the RS-485 cable using twisted-pair wire, such as Belden 1120A. The cable

must be voltage-rated for the installation.

5. When tightening terminals, ensure that the correct torque is applied: 0.5 to 0.6

N·m (0.37 to 0.44 ft·lb ) for connectors on main board, 0.22 to 0.26 N·m (0.16 to
0.19 ft·lb) for connectors on adapter boards (Figure 15).

+

Figure 15