8. Configure communication and addressing parameters using DIP switches. The E31
requires two addresses, one for each set of 42 current sensors and four auxiliary
inputs. See the Configuration section for more information.
9. Wire RS-485 communications (see diagrams in Wiring section).
10. Connect 0.333VAC current transducers (CTs) to the main conductors by snapping
CTs around lines, observing local codes regarding bending radius (optional;
Figures 9, 10).
Figure 11
V1 V2 V3 N
90-277 VAC
L - L
L - N
Line to Line (L-L) Voltage: 150 to 480 VAC
Line to Neutral (L-N) voltage: 90 to 277 VAC
Voltage taps are shared by both panels.
Panel 1
Panel 2
Figure 9
Figure 10
Set up Modbus registers 115-118 for CT scaling.
Use base + 1 address for Panel 2 setup.
Note: (+) represents black, (-) represents white
I1
I2
I3
IN
I1
I2
I3
IN
±
±
±
±
±
±
±
±
Panel 2
Panel 1
CT Input
(0-0.333 VAC)
CT Input
(0-0.333 VAC)
Recommended CT:
Veris Industries H6810, H6811, H6812 Series with 0.333VAC output.
Available in 100A max. to 2400A max.
Call a Veris sales rep if higher amperages are required.
11. Connect 2-wire 90-277VAC power to main power terminals. Observe polarity. For
the E31A and E31B, connect voltage lines to the voltage taps (Figure 11). Equip
voltage lines with fuses.