INSTALLATIoN GUIDe

troubleshootIng

Problem

Solution

Product is not communicating over Modbus daisy chain

• Check the unit Modbus address to ensure that each device on the daisy chain has a unique address.

• Check Parity.

• Check the communications wiring.

• Check that the daisy chain is properly terminated.

RX LED is solid

• Check for reversed polarity on Modbus comms.

• Check for sufficient biasing on the Modbus bus. Modbus physical specification calls for 450-650 Ω biasing. This is usually

provided by the master.

The main board has a fast flashing amber light

• Verify ribbon cable connectors are inserted in the correct orientation.

• If cables are correct, reset main board to re-initialize product.

The main board has a slow flashing amber light

• One or more channels is clipping. This can be caused by a signal greater than the split-core size or 277 V L-N, or by a signal

with high THD near the gain stage switching points (1.5 A and 10 A).

The main board has a flashing green light

• Everything is wired properly and the main board has power.

The main board is a flashing or solid red light

• Light may be red briefly while device powers up.

• If light is red for more the 60 sec. device has encountered a diagnostic event. Contact technical support.

Split-core product is reading zero for some values

• Device was unable to read split-core adapter boards on power up. Verify adapter boards are connected.

• Verify ribbon cable connectors are inserted in the correct orientation.

• Reset main board to re-initialize product.

Power factor reading is not as expected

• Verify voltage taps are connected in appropriate phase rotation.

• Verify phase rotation of breakers (firmware rev. 1.012 or higher allows for custom rotation if needed).

Current reading is not as expected, or reading is on different CT

number than expected

• Verify ribbon cable is fully seated and in the correct orientation.

Current is reading zero, even when small currents are still

flowing through circuit

• The product cuts off at 50 mA, and will set the reporting register to 0 mA for currents near or below this range.

E3x Config Tool returns Modbus error on read/write

• Verify using the latest release of E3x Config Tool as older versions may not support all features in current product firmware.

Latest version is available on our website http://www.veris.com/modbus.aspx

chIna rohs comPlIance InformatIon (efuP table)

部件名称

产品中有毒有害物质或元素的名称及含量Substances

铅 (Pb) 汞 (Hg)

镉 (Cd)

六价铬 (Cr(VI))

多溴联苯(PBB)

多溴二苯醚(PBDE)

电子线路板

X

O

O

O

O

O

O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.

X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.

Z000057-0A