INSTALLATIoN GUIDe
commIssIonIng
1. Reconnect power to the panel.
2. Configure installation mode using Modbus Register 6.
3. Configure CT scaling.
4. Configure alarms.
5. Configure demand.
Download the free E3x configuration tool from www.veris.com to commission the
device for operation.
safety
If Veris E31 products are used in installations with circuits higher than the product
ratings, the circuits must be kept segregated per UL508A Sec. 17.5.
Note: 277/480VAC Wye connected (center grounded) power systems operate
within the 300VAC line to neutral safety rating of the E3x series, and the
operational voltage limit (single-phase connection) as the line to neutral
voltage is 277VAC in such power systems. Corner-grounded delta 480VAC
systems would not qualify, as the actual line to earth voltage is 480VAC on
each leg, exceeding the E3x ratings.
Note: E3x internal circuitry (cables and CTs) are not circuits as defined by
UL508A, as they do not extend beyond the E3x itself without further safety/
fire isolation.
UL listed under standard 508 as an “open type device.”
Maximum ambient air temperature for use is 60°C.
Installation category: CAT III
The E31 Series must be installed in an appropriate electrical and fire enclosure per
local regulations.
For use in a Pollution Degree 2 or better environment only.
A Pollution Degree 2 environment must control conductive pollution and the
possibility of condensation or high humidity. Consideration must be given to the
enclosure, the correct use of ventilation, thermal properties of the equipment and the
relationship with the environment.
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the device may be impaired.
IEC/EN 61010-1
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on the
product.
recommended accessorIes
Part ID
Description
CBL008
Flat ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL016
Flat ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL017
Flat ribbon cable, 50 x 28 AWG, 5 ft. (1.5 m)
CBL018
Flat ribbon cable, 50 x 28 AWG, 6 ft. (1.8 m)
CBL019
Flat ribbon cable, 50 x 28 AWG, 8 ft. (2.4 m)
CBL020
Flat ribbon cable, 50 x 28 AWG, 10 ft. (3.0 m)
CBL021
Flat ribbon cable, 50 x 28 AWG, 20 ft. (6.1 m)
CBL022
Round ribbon cable, 50 x 28 AWG, 4 ft. (1.2 m)
CBL023
Round ribbon cable, 50 x 28 AWG, 10 ft. (3 m)
CBL024
Round ribbon cable, 50 x 28 AWG, 20 ft. (6 m)
CBL025
Flat ribbon cable, 50 x 28 AWG, 2 m
CBL026
Flat ribbon cable, 50 x 28 AWG, 4 m
CBL027
Flat ribbon cable, 50 x 28 AWG, 6 m
CBL031
Round ribbon cable, 50 x 28 AWG, 1.5 ft. (0.45 m)
CBL032
Round ribbon cable, 50 x 28 AWG, 2.5 ft. (0.76 m)
E31CT0
Six-pack 50 A CT, 6 ft. (1.8 m) lead
E31CT0R20
Six-pack 50 A CT, 20 ft. (6 m) lead
E31CT1
Six-pack 100 A CT, 6 ft. (1.8 m) lead
E31CT1R20
Six-pack 100 A CT, 20 ft. (6 m) lead
E31CT3
Single 200A CT, 6ft (1.8m) lead
E31CT3R20
Single 200A CT, 20ft (6m) lead
E31CTDB
2 E31 Adapter boards
AE001
E3x MCB Cover
AV01
Veris DIN Rail