HEATING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YZB03011
INDOOR COIL MODEL NO.
FC/MC/PC/UC36
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
800
1000
1200
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
34.3
2.5
4.0
35.3
2.4
4.4
36.3
2.2
4.8
70
33.3
2.8
3.5
34.3
2.6
3.8
35.3
2.5
4.2
80
32.3
3.1
3.1
33.3
2.9
3.4
34.3
2.7
3.7
47
60
29.8
2.4
3.6
30.7
2.3
3.9
31.5
2.2
4.3
70
29.3
2.7
3.2
30.0
2.6
3.4
30.7
2.4
3.7
80
28.8
3.0
2.8
29.3
2.8
3.1
29.9
2.6
3.3
40
60
27.7
2.4
3.4
28.6
2.3
3.7
29.5
2.2
4.0
70
27.1
2.7
3.0
27.9
2.6
3.2
28.7
2.4
3.5
80
26.6
3.0
2.6
27.2
2.8
2.8
27.8
2.7
3.1
30
60
22.3
2.2
2.9
23.7
2.2
3.2
25.1
2.1
3.5
70
22.0
2.5
2.6
23.3
2.4
2.9
24.6
2.3
3.1
80
21.7
2.7
2.4
22.9
2.6
2.6
24.1
2.6
2.8
17
60
17.2
2.2
2.3
18.2
2.1
2.5
19.2
2.1
2.7
70
17.4
2.4
2.1
18.3
2.4
2.3
19.2
2.3
2.4
80
17.6
2.7
1.9
18.4
2.6
2.1
19.1
2.5
2.2
10
60
16.4
2.1
2.3
17.2
2.1
2.4
18.0
2.1
2.5
70
15.9
2.4
2.0
16.7
2.3
2.1
17.5
2.3
2.3
80
15.4
2.6
1.7
16.2
2.6
1.9
17.0
2.5
2.0
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
MA12B
FC/MC36B
1.00
1.00
1.00
MV12B
FC/MC36B
0.98
0.98
1.00
MV16C
FC/MC36C
0.98
0.98
1.00
AHP30
–
1.00
1.00
1.00
AHP36
–
1.00
1.00
1.00
AV36
–
0.97
0.91
1.06
F*FP036
–
0.99
0.99
1.00
–
HC36
1.00
1.00
1.00
–
HD36
1.00
1.00
1.00