beautypg.com

York YZB018 THRU 060 User Manual

Page 34

background image

271457-YTG-B-0908

34

Johnson Controls Unitary Products

Multipliers for determining the performance with other indoor sections.

Continued on Page 35.

HEATING PERFORMANCE DATA

OUTDOOR UNIT MODEL NO.

YZB03011

INDOOR COIL MODEL NO.

FC/MC/PC/UC36

AIR TEMP.

ENTERING

OUTDOOR UNIT

AIR TEMP.

ENTERING

INDOOR COIL

ID CFM

800

1000

1200

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

60

60

34.3

2.5

4.0

35.3

2.4

4.4

36.3

2.2

4.8

70

33.3

2.8

3.5

34.3

2.6

3.8

35.3

2.5

4.2

80

32.3

3.1

3.1

33.3

2.9

3.4

34.3

2.7

3.7

47

60

29.8

2.4

3.6

30.7

2.3

3.9

31.5

2.2

4.3

70

29.3

2.7

3.2

30.0

2.6

3.4

30.7

2.4

3.7

80

28.8

3.0

2.8

29.3

2.8

3.1

29.9

2.6

3.3

40

60

27.7

2.4

3.4

28.6

2.3

3.7

29.5

2.2

4.0

70

27.1

2.7

3.0

27.9

2.6

3.2

28.7

2.4

3.5

80

26.6

3.0

2.6

27.2

2.8

2.8

27.8

2.7

3.1

30

60

22.3

2.2

2.9

23.7

2.2

3.2

25.1

2.1

3.5

70

22.0

2.5

2.6

23.3

2.4

2.9

24.6

2.3

3.1

80

21.7

2.7

2.4

22.9

2.6

2.6

24.1

2.6

2.8

17

60

17.2

2.2

2.3

18.2

2.1

2.5

19.2

2.1

2.7

70

17.4

2.4

2.1

18.3

2.4

2.3

19.2

2.3

2.4

80

17.6

2.7

1.9

18.4

2.6

2.1

19.1

2.5

2.2

10

60

16.4

2.1

2.3

17.2

2.1

2.4

18.0

2.1

2.5

70

15.9

2.4

2.0

16.7

2.3

2.1

17.5

2.3

2.3

80

15.4

2.6

1.7

16.2

2.6

1.9

17.0

2.5

2.0

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handler

Coil

MBH

KW

COP

MA12B

FC/MC36B

1.00

1.00

1.00

MV12B

FC/MC36B

0.98

0.98

1.00

MV16C

FC/MC36C

0.98

0.98

1.00

AHP30

1.00

1.00

1.00

AHP36

1.00

1.00

1.00

AV36

0.97

0.91

1.06

F*FP036

0.99

0.99

1.00

HC36

1.00

1.00

1.00

HD36

1.00

1.00

1.00