York YZB018 THRU 060 User Manual
Page 25
271457-YTG-B-0908
Johnson Controls Unitary Products
25
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on Page 26.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YZB03011
INDOOR COIL MODEL NO.
FC/MC/PC/UC36
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
57
62
62
67
72
65
T.C.
27.1
29.1
29.2
33.5
37.3
29.0
30.7
30.7
34.8
38.8
31.0
32.2
32.2
36.1
40.2
S.C.
26.7
23.3
20.0
20.6
16.9
28.7
26.6
22.6
23.0
18.3
30.7
29.9
25.1
25.3
19.7
K.W.
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
75
T.C.
26.2
27.9
27.8
31.7
35.7
28.1
29.3
29.1
33.0
37.0
29.9
30.7
30.5
34.3
38.2
S.C.
25.9
22.9
19.3
19.9
16.2
27.7
26.0
21.7
22.3
17.6
29.6
29.0
24.1
24.7
19.1
K.W.
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
85
T.C.
25.4
26.6
26.3
29.9
34.1
27.1
27.9
27.5
31.2
35.2
28.8
29.1
28.7
32.5
36.2
S.C.
25.1
22.6
18.5
19.1
15.6
26.8
25.3
20.8
21.7
17.0
28.4
28.1
23.2
24.2
18.4
K.W.
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
95
T.C.
24.5
25.4
24.8
28.1
32.6
26.1
26.5
25.9
29.4
33.4
27.7
27.6
27.0
30.7
34.2
S.C.
24.3
22.3
17.7
18.4
14.9
25.8
24.7
19.9
21.0
16.4
27.3
27.2
22.2
23.6
17.8
K.W.
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
105
T.C.
23.1
23.7
23.4
26.3
30.3
24.5
24.8
24.3
27.4
30.4
26.0
26.0
25.2
28.4
30.4
S.C.
22.9
21.4
17.2
17.8
14.2
24.3
23.5
19.4
20.2
16.9
25.7
25.6
21.6
22.7
19.5
K.W.
3.1
3.1
3.1
3.0
3.0
3.1
3.1
3.1
3.0
3.0
3.1
3.0
3.1
3.0
3.0
115
T.C.
21.7
22.0
21.9
24.6
28.2
23.0
23.2
22.6
25.4
27.4
24.3
24.4
23.4
26.1
26.7
S.C.
21.5
20.6
16.8
17.2
13.5
22.8
22.4
18.9
19.5
17.4
24.0
24.1
21.1
21.8
21.2
K.W.
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
125
T.C.
20.3
20.4
20.5
22.9
26.0
21.5
21.6
21.0
23.4
24.5
22.7
22.9
21.6
23.9
23.1
S.C.
20.1
19.8
16.4
16.5
12.9
21.3
21.2
18.4
18.8
17.9
22.4
22.7
20.5
21.0
22.9
K.W.
3.8
3.8
3.8
3.8
3.7
3.8
3.8
3.8
3.8
3.7
3.8
3.8
3.8
3.8
3.7
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MA12B
FC/MC36B
1.00
1.00
1.00
MV12B
FC/MC36B
0.99
1.00
0.96
MV16C
FC/MC36C
0.99
1.00
0.96
AHP30
–
1.00
1.00
1.00
AHP36
–
1.00
0.99
1.00
F2FP036
–
1.01
1.00
1.00
AV36
–
1.03
1.00
0.96
–
HC36
1.01
0.99
1.00
–
HD36
1.01
1.02
1.00