Texas Instruments TMS370 User Manual
Page 45
Editing the Configuration Parameters and Device Table
2-11
Program Algorithm:
If the family code is 10h (TMS370 EEPROM range), one of three pro-
gramming algorithms can be chosen—
program 1s, program 0s, or
program 1s and 0s. Using this parameter along with the block erase
parameter, you can optimize for programming speed or can mini-
mize the number of write erase cycles. This parameter is ignored for
any other family code and should be set to
program 0s only for clarity.
After you have entered the program algorithm, the programmer repeats
the setup configuration starting at Step 2 to allow you to enter up to five
address blocks. Press
to exit the loop after you have entered all the
address blocks you need. You must enter at least one set of
add device
parameters before exiting the command, or else the following warning
message is displayed.
Device parameters not complete, device not added.
Press any key to erase the warning message and return to the configura-
tion command menu.
After you have entered all of the above parameters correctly, the newly de-
fined device is added to the current device table and displayed in the de-
vice table window.
2.9
Editing the Configuration Parameters and Device Table — the Edit
Command
In the
edit mode, you can edit the configuration port # parameter field and the
current device table.
2.9.1
Editing the Configuration Parameters
From the configuration window press
for the edit command. Pressing
toggles you between the port # field and the device table, while pressing
in the port # field scrolls through the valid selections for the communication
port—port 1, or 2.
Press the
key when you are finished editing the parameters to record your
changes and to return you to the configuration command menu.
Note:
In order to edit any of the current device table parameters, you must display
the parameters (show ranges) and then use the designated function key to
edit the ranges window. Refer to subsection 2.9.2 for a complete description.