beautypg.com

3 parameter initial settings list – Toshiba LF516 User Manual

Page 102

background image


101

6 F 8 A 0 9 3 4

8.3 Parameter initial settings list

Unless otherwise specified, the default values for each parameter shown below are set when shipped from
the factory:

Parameter names

Default value

Excitation frequency

(*1)

Flow direction

NORMAL

Display 1

gal/min

Display 2

COUNT B

Display digit setting
(for Display 1 and Display 2)

1/1000

Custom coefficient

1.0

Custom unit

“ CUSTOM”(Head of character string is blank )

Range type

Single

Range 1

300 gal/min

Ranges 2 to 4

0 gal/min

Hysteresis 3.0

%

Damping constant

5.0 s

Rate-of-change limit

0.0 %

Control limit time

0.0 s

Low cutoff

1.0 %

Display low cutoff

LINEAR

Manual zero

0.0 %

4

−20mADC alarm output

4mA

Output low limit setting

4mA

Digital output 1

NO USE

Digital output 2

NO USE

DO1/DO2 active status

NormOPEN

Digital input

NO USE

DI detective level

H LEVEL

Count rate

100 gal

Pulse width setting mode

AUTO

Pulse width

5 ms

Preset count

00000000

Preset function

HOLD

High alarm On/Off

OFF

High alarm value

0.0 %

Low alarm On/Off

OFF

Low alarm value

0.0 %

High-High alarm On/Off

OFF

High-High alarm value

0.0 %

Low-Low alarm On/Off

OFF

Low-Low alarm value

0.0 %

Empty pipe alarm

NORMAL

Self-diagnosis On/Off

ON

Converter alarm

CONV ONLY

Fixed value output

OFF

Fixed value current

4mA

Fixed value pulse

0 pps

Password 000
LCD density adjustment

3

Switch position setting

BOTTOM

*1: See the setting values for each meter size in the table below.

This manual is related to the following products: