Installing the ups system, 1 preliminary installation information – Powerware 9330 User Manual
Page 27
![background image](/manuals/185869/27/background.png)
2--1
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Installing the UPS System
2.1
Preliminary Installation Information
WARNING:
Installation should be performed only by qualified personnel.
Refer to the following while installing the UPS system:
·
Refer to Appendix A of this manual for installation drawings and additional
installation notes.
·
Dimensions in this manual are in millimeters and inches.
·
Do not tilt the cabinets more than
10˚ during installation.
·
The conduit landing plates are to be removed to add conduit landing holes as
required. Plate material is 16 gauge steel (0.060 in. thick).
·
The cabinets must be installed on a level floor suitable for computer or
electronic equipment.
·
If perforated floor tiles are required for ventilation, place them in front of the
UPS. Refer to Table AA in Appendix A for equipment weight and point loading.
·
Details about control wiring are provided in each procedure for connecting
options and features. Drawing 164201300---2 and Tables X and Y in Appendix A
identify the control wiring terminations.
2