POWER WIRING INSTALLATION NOTES
164201300---1
A---8
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table K. Ratings & External Wiring Requirements for
Powerware 9330 (25 kVA---40 kVA)
Options Cabinet INPUT and BYPASS Transformers
Ratings 50/60 Hz
Basic unit ratings at
Voltage
Input
Conductor
g
0.7 lagging PF load
Series/
Model
kVA/KW
Input
Output
Input
Current
(Amps)
Minimum
Size
40/25
25/17.5
208
208
69.4
4
40/25
25/17.5
480
208
30
8
40/25
25/17.5
600
208
24
10
40/30
30/21
208
208
83
2
AC Input to UPS Rectifier
40/30
30/21
480
208
36
8
AC
AC Input to UPS Rectifier
Transformer
40/30
30/21
600
208
28.8
10
AC
INPUT
Transformer
(0.95min.PF)
3 1 d
40/35
35/24.5
208
208
97
1
(
)
3 , 1 gnd
40/35
35/24.5
480
208
42
6
40/35
35/24.5
600
208
33.6
8
40/40
40/28
208
208
111
1/0
40/40
40/28
480
208
48
6
40/40
40/28
600
208
38.5
8
40/25
25/17.5
208
208
69.4
4
40/25
25/17.5
480
208
30
8
40/25
25/17.5
600
208
24
10
40/30
30/21
208
208
83
2
AC Input to UPS Bypass
40/30
30/21
480
208
36
8
AC
AC Input to UPS Bypass
Transformer
40/30
30/21
600
208
28.8
10
AC
INPUT
Transformer
Full Load Current
3 1 N
l 1
d
40/35
35/24.5
208
208
97
1
3 , 1 Neutral, 1 gnd
40/35
35/24.5
480
208
42
6
40/35
35/24.5
600
208
33.6
8
40/40
40/28
208
208
111
1/0
40/40
40/28
480
208
48
6
40/40
40/28
600
208
33.5
8