Ab c d – Powerware 9330 User Manual

Page 172

background image

DESCRIPTION:

DATE:

DRAWING NO:

1 of 17

SHEET:

REVISION:

F

NOTE:

Callout letter

and

map to drawing #164201300---6

,

, ,

111501

A

B

C

D

164201300---1

POWER WIRING INSTALLATION NOTES

A---2

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table A. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9330---20/10

(Without Options Cabinet)

Ratings

Units

Rating 50/60 Hz

Basic unit ratings at

0.7 lagging PF load

KVA

KW

10

7

gg g

INPUT/OUTPUT

VOLTAGE

208

AC Input to UPS Rectifier

(0.95min.PF)

Amps*

28

AC

AC Input to UPS Rectifier

(0.95min.PF)

3 , 1 gnd

Amps*

28

AC

INPUT

3 , 1 gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

8 (1)

*(Maximum amps includes full load current plus

battery recharge current)

AC

AC Input to Module Bypass (UPS Bypass)

Full Load Current

3 , (1) Neutral, (1) gnd

Amps

27.8

AC

INPUT

Full Load Current

3 , (1) Neutral, (1) gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

8 (1)

DC

INPUT

DC Input from External Battery Source to UPS

(1) positive, (1) negative, (1) gnd

VDC (Nominal)

Amps

288

26

INPUT

( ) pos t e, ( ) egat e, ( ) g d

Minimum conductor size (number per pole) (See note 8)

AWG or kcmil(ea)

10 (1)

AC

AC Output to Critical Load

Full Load Current 3  (1) Neutral (1) gnd

Amps

27.8

AC

OUTPUT

Full Load Current 3 , (1) Neutral, (1) gnd

Minimum conductor size (number per  )

AWG or kcmil(ea)

8 (1)

Read and understand the following notes while planning your installation:

1.

Refer to national and local electrical codes for acceptable external wiring practices.

2.

The bypass feed into this equipment utilizes four wires. The rectifier feed into this

equipment utilizes three wires. However, the phases must be symmetrical about ground

(i.e., from a Wye source) for proper equipment operation. Failure to follow these

instructions will void the product warranty.

3.

Material and labor for external wiring requirements are to be provided by designated

personnel.

4.

For external wiring, use 90°C copper wire. See the appropriate column in Tables A

through M.

5.

Wire ampacities are chosen from Table 310---16 of the NEC.

6.

A bypass neutral feeder must be supplied.

7.

Refer to Section I of this manual for installation Instructions.

8.

UPS systems not using an external battery source are supplied with internal batteries

prewired to the UPS at the factory. External Line-up and Match Battery cabinets are

provided with with quick disconnect cables for connection to the UPS. No external wiring

is required for Line-up and Match batery cabinets. All products can be connected to an

external battery source through the DC connections terminal block. An external DC

ground is established through the grounding terminal in the bottom of the cabinet.