PHYSICAL FEATURES AND REQUIREMENTS
164201300---3
A---25
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
6.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
0---40˚C (32---104˚F)
Recommended Operating Range: 20---25˚C (68---77˚F)
Maximum Relative Humidity:
95%, noncondensing
The UPS ventilation requirements are shown in Table AC.
Table AC. Air Conditioning or Ventilation Requirements
During Full Load Operation
Powerware 9330 (10 kVA--40 kVA)
Ratings
Input/Output Voltage
Heat Rejection*
BTU/hr ¢ 1000/hr (Kg---cal/hr)
208/208
2.4 (0.6)
10 KVA
480/208
3.1 (0.8)
480/480, 600/208
3.6 (0.9)
208/208
3.5 (0.9)
15 KVA
480/208
4.6 (1.1)
480/480, 600/208
5.3 (1.3)
208/208
4.7 (1.2)
20 KVA
480/208, 600/208
6.1 (1.5)
480/480
7.1 (1.8)
208/208
5.9 (1.5)
25 KVA
480/208, 600/208
7.7 (1.9)
480/480
8.9 (2.2)
208/208
7.1 (1.8)
30 KVA
480/208, 600/208
9.2 (2.3)
480/480
10.7 (2.7)
208/208
8.3 (2.1)
35 KVA
480/208, 600/208
10.8 (2.7)
480/480
12.5 (3.1)
208/208
9.5 (2.4)
40 KVA
480/208, 600/208
12.4 (3.1)
480/480
14.3 (3.6)