POWER WIRING INSTALLATION NOTES
164201300---1
A---4
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table D. Ratings & External Wiring Requirements for
Powerware 9330 (10 kVA---20 kVA)
Options Cabinet INPUT and BYPASS Transformers
Ratings 50/60 Hz
Basic unit ratings at
Voltage
Input
Conductor
g
0.7 lagging PF load
Series/
Model
kVA/KW
Input
Output
Input
Current
(Amps)
Minimum
Size
20/10
10/7
208
208
27.8
8
20/10
10/7
480
208
12
14
20/10
10/7
600
208
9.6
14
AC Input to UPS Rectifier
20/15
15/10.5
208
208
41.6
6
AC
INPUT
p
Transformer
(0 95min PF)
20/15
15/10.5
480
208
18
12
INPUT (0.95min.PF)
3 , 1 gnd
20/15
15/10.5
600
208
14.4
12
3 , 1 gnd
20/20
20/14
208
208
55.5
4
20/20
20/14
480
208
24
10
20/20
20/14
600
208
19.2
12
20/10
10/7
208
208
27.8
8
20/10
10/7
480
208
12
14
20/10
10/7
600
208
9.6
14
AC Input to UPS Bypass
20/15
15/10.5
208
208
41.6
6
AC
INPUT
p
yp
Transformer
Full Load Current
20/15
15/10.5
480
208
18
12
INPUT Full Load Current
3 , 1 Neutral, 1 gnd
20/15
15/10.5
600
208
14.4
12
3 , 1 Neutral, 1 gnd
20/20
20/14
208
208
55.5
4
20/20
20/14
480
208
24
10
20/20
20/14
600
208
19.2
12