DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION: G
1 of 5
051502
CUSTOMER INTERFACE WIRING
INSTALLATION NOTES
164201300---2
A---19
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
1.
Use Class 1 wiring methods (as defined by the NEC) for control wiring. Install the control
wiring in separate conduit from the power wiring. The wire should be rated at 150 volts,
5 amp minimum.
2.
Refer to Tables X, Y, and Z and to Chapters 2, 5 and 6 of this manual for customer
interface wiring.
Table X. Customer Interface Inputs and Outputs
Terminal TB2
Name
Description
1
BLDG ALARM 1
Programmable UPS alarm. Activated by a remote dry
2
BLDG ALARM 1 RTN
Programmable UPS alarm. Activated by a remote dry
contact closure.
3
BLDG ALARM 2
Programmable UPS alarm. Activated by a remote dry
4
BLDG ALARM 2 RTN
Programmable UPS alarm. Activated by a remote dry
contact closure.
5
BLDG ALARM 3
Programmable UPS alarm. Activated by a remote dry
6
BLDG ALARM 3 RTN
Programmable UPS alarm. Activated by a remote dry
contact closure.
7
BLDG ALARM 4
Programmable UPS alarm. Activated by a remote dry
8
BLDG ALARM 4 RTN
Programmable UPS alarm. Activated by a remote dry
contact closure.
Terminal TB4
1
CAN H
2
CAN L
Parallel CAN Input
3
RTN
Parallel CAN Input
Terminal TB5
1
Not Used
2
Not Used
3
EXTERNAL EPO
Dry contact used to activate remote EPO of UPS
4
EXTERNAL EPO RTN
Dry contact used to activate remote EPO of UPS.
5
Not Used
6
RTN
Terminal TB6
1
RELAY 1 RTN
2
RELAY 1 NO
General purpose NO and NC relay contacts.
3
RELAY 1 NC
General purpose NO and NC relay contacts.
Terminal TB7
1
RELAY 2 RTN
2
RELAY 2 NO
General purpose NO and NC relay contacts.
3
RELAY 2 NC
General purpose NO and NC relay contacts.
X---Slot 4
Terminal
1
UTIL_FAIL
Input used to indicate utility power failure
2
ON_BYPASS
Input used to indicate On Bypass status of UPS
3
BATTERY_LOW
Contacts used to indicate Battery Low status of UPS