POWER WIRING INSTALLATION NOTES
A
B
C
D
A---3
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table B. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9330---20/15
(Without Options Cabinet)
Ratings
Units
Rating 50/60 Hz
Basic unit ratings at
0.7 lagging PF load
KVA
KW
15
10.5
gg g
INPUT/OUTPUT
VOLTAGE
208
AC Input to UPS Rectifier
(0.95min.PF)
Amps*
40
AC
AC Input to UPS Rectifier
(0.95min.PF)
3 , 1 gnd
Amps*
40
AC
INPUT
3 , 1 gnd
Minimum conductor size (number per )
AWG or kcmil(ea)
8 (1)
*(Maximum amps includes full load current plus
battery recharge current)
AC
AC Input to Module Bypass (UPS Bypass)
Full Load Current
3 , (1) Neutral, (1) gnd
Amps
41.6
AC
INPUT
Full Load Current
3 , (1) Neutral, (1) gnd
Minimum conductor size (number per )
AWG or kcmil(ea)
6 (1)
DC
INPUT
DC Input from External Battery Source to UPS
(1) positive, (1) negative, (1) gnd
VDC (Nominal)
Amps
288
39
INPUT
( ) pos t e, ( ) egat e, ( ) g d
Minimum conductor size (number per pole) (See note 8)
AWG or kcmil(ea)
8 (1)
AC
AC Output to Critical Load
Full Load Current 3 (1) Neutral (1) gnd
Amps
41.6
AC
OUTPUT
Full Load Current 3 , (1) Neutral, (1) gnd
Minimum conductor size (number per )
AWG or kcmil(ea)
6 (1)
Table C. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9330---20/20
(Without Options Cabinet)
Ratings
Units
Rating 50/60 Hz
Basic unit ratings at
0.7 lagging PF load
KVA
KW
20
14
gg g
INPUT/OUTPUT
VOLTAGE
208
AC Input to UPS Rectifier
(0.95min.PF)
Amps*
52
AC
AC Input to UPS Rectifier
(0.95min.PF)
3 , 1 gnd
Amps*
52
AC
INPUT
3 , 1 gnd
Minimum conductor size (number per )
AWG or kcmil(ea)
6 (1)
*(Maximum amps includes full load current plus
battery recharge current)
AC
AC Input to Module Bypass (UPS Bypass)
Full Load Current
3 , (1) Neutral, (1) gnd
Amps
55.5
AC
INPUT
Full Load Current
3 , (1) Neutral, (1) gnd
Minimum conductor size (number per )
AWG or kcmil(ea)
4 (1)
DC
INPUT
DC Input from External Battery Source to UPS
(1) positive, (1) negative, (1) gnd
VDC (Nominal)
Amps
288
52
INPUT
( ) pos t e, ( ) egat e, ( ) g d
Minimum conductor size (number per pole) (See note 8)
AWG or kcmil(ea)
6 (1)
AC
AC Output to Critical Load
Full Load Current 3 (1) Neutral (1) gnd
Amps
55.5
AC
OUTPUT
Full Load Current 3 , (1) Neutral, (1) gnd
Minimum conductor size (number per )
AWG or kcmil(ea)
4 (1)