Powerware 9330 User Manual
Page 175

DESCRIPTION:
DATE:
DRAWING NO:
4 of 17
SHEET:
REVISION: E
NOTE:
Callout letter
and
map to drawing #164201300---6
,
, ,
071501
164201300---1
POWER WIRING INSTALLATION NOTES
D
D
A---5
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table E. Ratings & External Wiring Requirements for
Powerware 9330 (10 kVA---20 kVA)
Options Cabinet OUTPUT Transformer
Ratings 50/60 Hz
Basic unit ratings at
Voltage
Output
Conductor
g
0.7 lagging PF load
Series/
Model
kVA/KW
Input
Output
Output
Current
(Amps)
Minimum
Size
20/10
9.5/6.65
208
208
26.4
10
AC Output from
20/10
9.5/6.65
208
480
11.4
14
AC
OUTPUT
AC Output from
Output Transformer
to Critical Load
20/15
14.25/10
208
208
39.6
8
OUTPUT to Critical Load
(0.95min.PF)
20/15
14.25/10
208
480
17
12
(0.95min.PF)
3 , 1 Neutral, 1 gnd
20/20
19/13.3
208
208
52.7
6
g
20/20
19/13.3
208
480
22.8
10
Table F. Ratings & External Wiring Requirements for
Powerware 9330 (10 kVA---20 kVA)
Options Cabinet OUTPUT Without Output Transformer
Ratings 50/60 Hz
Basic unit ratings at
Voltage
Output
Conductor
g
0.7 lagging PF load
Series/
Model
kVA/KW
Input
Output
Output
Current
(Amps)
Minimum
Size
AC
AC Output from Output
20/10
10/7
208
208
27.8
8
AC
OUTPUT
p
p
to Critical Load
(0 95min PF)
20/15
15/10.5
208
208
41.6
6
(0.95min.PF)
3 , 1 Neutral, 1 gnd
20/20
20/14
208
208
55.5
4